NEC Table 430.248 — Single-Phase AC Motors Full-Load Current

Single-phase motors running at usual speeds with normal torque characteristics.

A 1 HP single-phase motor draws 8 A at 230 V, and a 5 HP motor draws 28 A at 230 V. Use these values, not the nameplate, to size conductors and short-circuit protection.

Full-load current in amps — single-phase ac motors
Horsepower115 V200 V208 V230 V
1/6 HP4.42.52.42.2
1/4 HP5.83.33.22.9
1/3 HP7.24.143.6
1/2 HP9.85.65.44.9
3/4 HP13.87.97.66.9
1 HP169.28.88
1 1/2 HP2011.51110
2 HP2413.813.212
3 HP3419.618.717
5 HP5632.230.828
7 1/2 HP80464440
10 HP10057.55550

Motor wire & breaker size calculator

Loading calculator…

Frequently asked questions

How many amps does a 1 HP single-phase ac motor draw?

A 1 HP single-phase motor draws 8 A at 230 V. 16 A at 115 V, 9.2 A at 200 V, 8.8 A at 208 V, 8 A at 230 V.

Should I use the nameplate amps or the table amps?

Use the table full-load current for sizing branch-circuit conductors, the short-circuit and ground-fault protective device, and the disconnect (430.6(A)(1)). Use the motor nameplate current only for sizing the separate overload protection.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.