1 1/2 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 1 1/2 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 1 1/2 HP motor draws 6 A at 230 V and 3 A at 460 V three-phase; 20 A at 115 V and 10 A at 230 V single-phase.

1 1/2 HP three-phase motor

1 1/2 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
115 V12 A15.0 A14 AWG30 A25 A
200 V6.9 A8.6 A14 AWG20 A15 A
208 V6.6 A8.2 A14 AWG20 A15 A
230 V6 A7.5 A14 AWG15 A15 A
460 V3 A3.8 A14 AWG15 A15 A
575 V2.4 A3.0 A14 AWG15 A15 A

1 1/2 HP single-phase motor

1 1/2 HP single-phase motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
115 V20 A25.0 A12 AWG50 A35 A
200 V11.5 A14.4 A14 AWG30 A25 A
208 V11 A13.8 A14 AWG30 A20 A
230 V10 A12.5 A14 AWG25 A20 A

1 1/2 HP DC motor

1 1/2 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
120 V13.2 A16.5 A
180 V8.3 A10.4 A
240 V6.6 A8.2 A

1 1/2 HP two-phase motor

1 1/2 HP two-phase, 4-wire motor
VoltageFull-load amps
115 V9 A
230 V4.5 A
460 V2.3 A
575 V1.8 A

1 1/2 HP is 1.12 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 1 1/2 HP motor draw?

A 1 1/2 HP motor draws 6 A at 230 V and 3 A at 460 V three-phase; 20 A at 115 V and 10 A at 230 V single-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 1 1/2 HP three-phase motor at 460 V?

Full-load current is 3 A, so conductors need at least 3.8 A of ampacity: 14 AWG copper at 75°C. The inverse-time breaker may be up to 15 A and a dual-element time-delay fuse up to 15 A.

What size wire for a 1 1/2 HP single-phase motor at 230 V?

10 A × 125% = 12.5 A, so 14 AWG copper is the minimum, with a breaker no larger than 25 A. At 115 V the current doubles to 20 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.