EMT Conduit Fill Chart

Electrical Metallic Tubing — NEC Article 358. Thin-wall galvanized steel tubing joined with set-screw or compression fittings. The default raceway for commercial branch circuits and exposed indoor work.

1/2-inch EMT holds 9 #12 THHN conductors; 3/4-inch holds 16. Counts assume 40% fill with all conductors the same size.

EMT fill calculator

Loading calculator…

EMT sizes

One page per trade size, with counts for every insulation type side by side.

EMT fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in EMT — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG147121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG1134712192532
2/0 AWG1123610162026
3/0 AWG111358131722
4/0 AWG11147111418
250 kcmil1113691115
300 kcmil113571013
350 kcmil11146911
400 kcmil11146810
500 kcmil1113568
600 kcmil112457
700 kcmil111346
750 kcmil111345
800 kcmil11345
900 kcmil11334
1000 kcmil11234

EMT fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in EMT — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG81525435896168254332424
12 AWG61119334574129195255326
10 AWG581424335596145190243
8 AWG2581318305381105135
6 AWG136101422396078100
4 AWG1247101628435672
3 AWG113681424364861
2 AWG113571120314051
1 AWG11145815233038
1/0 AWG1134713192532
2/0 AWG1123610162127
3/0 AWG111359131722
4/0 AWG11147111418
250 kcmil1113691215
300 kcmil1113581013
350 kcmil11247911
400 kcmil11146810
500 kcmil1113568
600 kcmil112456
700 kcmil111346
750 kcmil111345
800 kcmil11345
900 kcmil11334
1000 kcmil11234

EMT fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in EMT — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG81525435896168254332424
12 AWG61119334574129195255326
10 AWG581424335596145190243
8 AWG2581318305381105135
6 AWG1348111832486381
4 AWG113681324364760
3 AWG113571220314052
2 AWG112461017263444
1 AWG1134712182431
1/0 AWG1123610162026
2/0 AWG111359131722
3/0 AWG11247111519
4/0 AWG1113691216
250 kcmil113571013
300 kcmil11146811
350 kcmil11146710
400 kcmil1113579
500 kcmil1113467
600 kcmil111346
700 kcmil11345
750 kcmil11345
800 kcmil11335
900 kcmil11234
1000 kcmil11134

EMT fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in EMT — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG471120274680120157201
12 AWG36917233866100131167
10 AWG2581318305381105135
8 AWG114791628425570
6 AWG113581322344456
4 AWG112461017263444
3 AWG11145915233038
2 AWG1134713202633
1 AWG111359131722
1/0 AWG11247111519
2/0 AWG11146101317
3/0 AWG1113581114
4/0 AWG11357912
250 kcmil1113579
300 kcmil1113568
350 kcmil1113467
400 kcmil112457
500 kcmil111346
600 kcmil11345
700 kcmil11234
750 kcmil11134
800 kcmil11134
900 kcmil11133
1000 kcmil11123

EMT internal diameter and area

EMT internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
1/2"160.6220.3040.1610.0940.1220.182
3/4"210.8240.5330.2820.1650.2130.320
1"271.0490.8640.4580.2680.3460.518
1-1/4"351.3801.4960.7930.4640.5980.898
1-1/2"411.6102.0361.0790.6310.8141.222
2"532.0673.3561.7791.0401.3422.014
2-1/2"632.7315.8583.1051.8162.3433.515
3"783.3568.8464.6882.7423.5385.308
3-1/2"913.83411.5456.1193.5794.6186.927
4"1034.33414.7537.8194.5735.9018.852

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch EMT?

9 conductors of 12 AWG THHN/THWN-2, or 6 of the thicker THW. In 3/4-inch EMT the count rises to 16 THHN.

How many #10 wires fit in 1/2-inch EMT?

5 conductors of 10 AWG THHN in 1/2-inch, and 10 in 3/4-inch.

What is the inside diameter of 3/4-inch EMT?

0.824 inches, giving a total internal area of 0.533 in² and 0.213 in² of usable area at 40% fill.

What is the largest wire that fits in 4-inch EMT?

4-inch EMT holds 8 conductors of 500 kcmil THHN or 4 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.