Rigid Metal (RMC) Conduit Fill Chart

Rigid Metal Conduit (RMC) — NEC Article 344. Threaded heavy-wall galvanized steel (or aluminum) conduit. The most protective raceway; used for services, hazardous locations and anywhere subject to severe physical damage.

1/2-inch Rigid Metal Conduit holds 9 #12 THHN conductors; 3/4-inch holds 16. Counts assume 40% fill with all conductors the same size.

Rigid Metal Conduit fill calculator

Loading calculator…

Rigid Metal Conduit sizes

One page per trade size, with counts for every insulation type side by side.

Rigid Metal Conduit fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in Rigid Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG13223663851402003094125318331202
12 AWG916264662102146225301387608877
10 AWG6101729396492142189244383552
8 AWG3691622375382109140221318
6 AWG147121627385979101159230
4 AWG124710162336486298141
3 AWG11368142031415383120
2 AWG11357111726344470100
1 AWG111458121925335174
1/0 AWG11347101621274363
2/0 AWG1123681318233652
3/0 AWG1113571115193043
4/0 AWG11146912162536
250 kcmil11135710132029
300 kcmil1113468111725
350 kcmil112357101522
400 kcmil11135781320
500 kcmil11124571116
600 kcmil111346913
700 kcmil111345811
750 kcmil111345711
800 kcmil11234710
900 kcmil1113469
1000 kcmil1113468

Rigid Metal Conduit fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in Rigid Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG91525445998140215288370581839
12 AWG71219334575107165221284446644
10 AWG591425345680123164212332480
8 AWG358141931446891118185267
6 AWG13610142333516887137197
4 AWG124710162437496399143
3 AWG11368142031415384121
2 AWG11357121726354570101
1 AWG111459121926335276
1/0 AWG11347101622284464
2/0 AWG1123691318233753
3/0 AWG1113571115193044
4/0 AWG11246912162536
250 kcmil11135710132030
300 kcmil1113469111825
350 kcmil112367101522
400 kcmil11135791420
500 kcmil11124571116
600 kcmil111346913
700 kcmil111345811
750 kcmil111345711
800 kcmil11234710
900 kcmil1113469
1000 kcmil1113468

Rigid Metal Conduit fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in Rigid Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG91525445998140215288370581839
12 AWG71219334575107165221284446644
10 AWG591425345680123164212332480
8 AWG358141931446891118185267
6 AWG1358111827415571111160
4 AWG11368142031415383120
3 AWG11357121726354571103
2 AWG1124610142230386087
1 AWG11347101521274261
1/0 AWG1123681318233652
2/0 AWG1113571115193144
3/0 AWG11246913162637
4/0 AWG11135810142131
250 kcmil1113468111725
300 kcmil11235791522
350 kcmil11135681319
400 kcmil11134671217
500 kcmil11113561014
600 kcmil111345812
700 kcmil11234710
750 kcmil11134710
800 kcmil1113469
900 kcmil1113368
1000 kcmil1112358

Rigid Metal Conduit fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in Rigid Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG471221284666102136176276398
12 AWG36101723385585113146229330
10 AWG358141931446891118185267
8 AWG124710162336486197139
6 AWG11368131829384977112
4 AWG1124610142230386087
3 AWG111459121926345376
2 AWG11347111723294666
1 AWG1113571115193044
1/0 AWG112461013172638
2/0 AWG11145811142333
3/0 AWG11134710122028
4/0 AWG113468111724
250 kcmil11134681318
300 kcmil11124571116
350 kcmil11114561015
400 kcmil111346913
500 kcmil111345811
600 kcmil1113469
700 kcmil1113368
750 kcmil1113358
800 kcmil1112357
900 kcmil1111357
1000 kcmil1111346

Rigid Metal Conduit internal diameter and area

Rigid Metal Conduit internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
1/2"160.6320.3140.1660.0970.1260.188
3/4"210.8360.5490.2910.1700.2200.329
1"271.0630.8870.4700.2750.3550.532
1-1/4"351.3941.5260.8090.4730.6100.916
1-1/2"411.6242.0711.0980.6420.8281.243
2"532.0833.4081.8061.0561.3632.045
2-1/2"632.4894.8662.5791.5081.9462.920
3"783.0907.4993.9742.3253.0004.499
3-1/2"913.57010.0105.3053.1034.0046.006
4"1034.05012.8826.8273.9935.1537.729
5"1295.07320.21210.7126.2668.08512.127
6"1556.09329.15815.4549.03911.66317.495

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch Rigid Metal Conduit?

9 conductors of 12 AWG THHN/THWN-2, or 7 of the thicker THW. In 3/4-inch Rigid Metal Conduit the count rises to 16 THHN.

How many #10 wires fit in 1/2-inch Rigid Metal Conduit?

6 conductors of 10 AWG THHN in 1/2-inch, and 10 in 3/4-inch.

What is the inside diameter of 3/4-inch Rigid Metal Conduit?

0.836 inches, giving a total internal area of 0.549 in² and 0.220 in² of usable area at 40% fill.

What is the largest wire that fits in 6-inch Rigid Metal Conduit?

6-inch Rigid Metal Conduit holds 16 conductors of 500 kcmil THHN or 8 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.