1/4 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 1/4 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 1/4 HP motor draws 5.8 A at 115 V and 2.9 A at 230 V single-phase.

1/4 HP single-phase motor

1/4 HP single-phase motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
115 V5.8 A7.2 A14 AWG15 A15 A
200 V3.3 A4.1 A14 AWG15 A15 A
208 V3.2 A4.0 A14 AWG15 A15 A
230 V2.9 A3.6 A14 AWG15 A15 A

1/4 HP DC motor

1/4 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
90 V4 A5.0 A
120 V3.1 A3.9 A
180 V2 A2.5 A
240 V1.6 A2.0 A

1/4 HP is 0.19 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 1/4 HP motor draw?

A 1/4 HP motor draws 5.8 A at 115 V and 2.9 A at 230 V single-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire for a 1/4 HP single-phase motor at 230 V?

2.9 A × 125% = 3.6 A, so 14 AWG copper is the minimum, with a breaker no larger than 15 A. At 115 V the current doubles to 5.8 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.