Motor Full-Load Amps (FLA) Chart

Full-load current of AC and DC motors by horsepower and voltage, with the conductor, breaker and fuse sizes that follow from it.

Three-phase at 460 V: 1 HP = 2.1 A · 5 HP = 7.6 A · 10 HP = 14 A · 25 HP = 34 A · 50 HP = 65 A · 100 HP = 124 A. At 230 V the current doubles; at 208 V multiply by 2.2.

Motor wire & breaker size calculator

Loading calculator…

Motor current tables

Three-phase motor amps — common voltages

Three-phase induction motor full-load current (amps)
Horsepower208 V230 V460 V575 V
1/2 HP2.42.21.10.9
3/4 HP3.53.21.61.3
1 HP4.64.22.11.7
1 1/2 HP6.6632.4
2 HP7.56.83.42.7
3 HP10.69.64.83.9
5 HP16.715.27.66.1
7 1/2 HP24.222119
10 HP30.8281411
15 HP46.2422117
20 HP59.4542722
25 HP74.8683427
30 HP88804032
40 HP1141045241
50 HP1431306552
60 HP1691547762
75 HP2111929677
100 HP27324812499
125 HP343312156125
150 HP396360180144
200 HP528480240192
250 HP302242
300 HP361289
350 HP414336
400 HP477382
450 HP515412
500 HP590472

Single-phase motor amps

Single-phase AC motor full-load current (amps)
Horsepower115 V200 V208 V230 V
1/6 HP4.42.52.42.2
1/4 HP5.83.33.22.9
1/3 HP7.24.143.6
1/2 HP9.85.65.44.9
3/4 HP13.87.97.66.9
1 HP169.28.88
1 1/2 HP2011.51110
2 HP2413.813.212
3 HP3419.618.717
5 HP5632.230.828
7 1/2 HP80464440
10 HP10057.55550

From FLA to wire and breaker size

  1. Look up the table current for the horsepower and voltage — not the nameplate.
  2. Conductors: ampacity ≥ 125% of FLA (430.22).
  3. Short-circuit protection: breaker ≤ 250% or time-delay fuse ≤ 175% of FLA, next standard size up permitted (430.52).
  4. Overloads: ≤ 125% of nameplate current for motors with service factor 1.15 or more or 40°C rise; 115% for all others (430.32).
  5. Disconnect: horsepower-rated, or at least 115% of FLA (430.110).

By horsepower

Frequently asked questions

Should I use the nameplate amps or the table amps?

Use the table full-load current for sizing branch-circuit conductors, the short-circuit and ground-fault protective device, and the disconnect (430.6(A)(1)). Use the motor nameplate current only for sizing the separate overload protection.

How do I size wire for a motor?

Branch-circuit conductors for a single motor must have an ampacity of at least 125% of the table full-load current. A 10 HP, 460 V three-phase motor is 14 A, so conductors need 17.5 A: 14 AWG copper. For several motors on one feeder, take 125% of the largest plus 100% of the rest.

How big can the breaker be for a motor?

For an inverse-time breaker, up to 250% of full-load current; for dual-element time-delay fuses, 175%; for non-time-delay fuses, 300%; for instantaneous-trip breakers, 800% (1100% for Design B energy-efficient motors). If the result is not a standard size, the next standard size up is permitted.

How many amps does a 1 HP motor draw?

16 A at 115 V and 8 A at 230 V single-phase; 4.2 A at 230 V and 2.1 A at 460 V three-phase.

Why can a motor breaker be larger than the wire ampacity?

Because the breaker only provides short-circuit and ground-fault protection and must ride through starting inrush of six times running current or more. Overload protection of the motor and its conductors is provided separately by the overload relay or the motor’s thermal protector.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.