7 1/2 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 7 1/2 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 7 1/2 HP motor draws 22 A at 230 V and 11 A at 460 V three-phase; 80 A at 115 V and 40 A at 230 V single-phase.

7 1/2 HP three-phase motor

7 1/2 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V25.3 A31.6 A10 AWG70 A45 A
208 V24.2 A30.2 A10 AWG70 A45 A
230 V22 A27.5 A10 AWG60 A40 A
460 V11 A13.8 A14 AWG30 A20 A
575 V9 A11.2 A14 AWG25 A20 A

7 1/2 HP single-phase motor

7 1/2 HP single-phase motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
115 V80 A100.0 A3 AWG200 A150 A
200 V46 A57.5 A6 AWG125 A90 A
208 V44 A55.0 A6 AWG110 A80 A
230 V40 A50.0 A8 AWG100 A70 A

7 1/2 HP DC motor

7 1/2 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
120 V58 A72.5 A
240 V29 A36.2 A
500 V13.6 A17.0 A
550 V12.2 A15.2 A

7 1/2 HP two-phase motor

7 1/2 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V19 A
460 V9 A
575 V8 A

7 1/2 HP is 5.59 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 7 1/2 HP motor draw?

A 7 1/2 HP motor draws 22 A at 230 V and 11 A at 460 V three-phase; 80 A at 115 V and 40 A at 230 V single-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 7 1/2 HP three-phase motor at 460 V?

Full-load current is 11 A, so conductors need at least 13.8 A of ampacity: 14 AWG copper at 75°C. The inverse-time breaker may be up to 30 A and a dual-element time-delay fuse up to 20 A.

What size wire for a 7 1/2 HP single-phase motor at 230 V?

40 A × 125% = 50.0 A, so 8 AWG copper is the minimum, with a breaker no larger than 100 A. At 115 V the current doubles to 80 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.