3 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 3 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 3 HP motor draws 9.6 A at 230 V and 4.8 A at 460 V three-phase; 34 A at 115 V and 17 A at 230 V single-phase.

3 HP three-phase motor

3 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V11 A13.8 A14 AWG30 A20 A
208 V10.6 A13.2 A14 AWG30 A20 A
230 V9.6 A12.0 A14 AWG25 A20 A
460 V4.8 A6.0 A14 AWG15 A15 A
575 V3.9 A4.9 A14 AWG15 A15 A

3 HP single-phase motor

3 HP single-phase motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
115 V34 A42.5 A8 AWG90 A60 A
200 V19.6 A24.5 A12 AWG50 A35 A
208 V18.7 A23.4 A12 AWG50 A35 A
230 V17 A21.2 A12 AWG45 A30 A

3 HP DC motor

3 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
120 V25 A31.2 A
180 V16 A20.0 A
240 V12.2 A15.2 A

3 HP two-phase motor

3 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V8.3 A
460 V4.2 A
575 V3.3 A

3 HP is 2.24 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 3 HP motor draw?

A 3 HP motor draws 9.6 A at 230 V and 4.8 A at 460 V three-phase; 34 A at 115 V and 17 A at 230 V single-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 3 HP three-phase motor at 460 V?

Full-load current is 4.8 A, so conductors need at least 6.0 A of ampacity: 14 AWG copper at 75°C. The inverse-time breaker may be up to 15 A and a dual-element time-delay fuse up to 15 A.

What size wire for a 3 HP single-phase motor at 230 V?

17 A × 125% = 21.2 A, so 12 AWG copper is the minimum, with a breaker no larger than 45 A. At 115 V the current doubles to 34 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.