NEC Table 310.16 — Conductor Ampacity

Not more than three current-carrying conductors in a raceway, cable or directly buried, 30°C (86°F) ambient. The everyday table — formerly numbered 310.15(B)(16).

Most-used values (copper, 75°C): 14 AWG 20 A · 12 AWG 25 A · 10 AWG 35 A · 8 AWG 50 A · 6 AWG 65 A · 4 AWG 85 A · 3 AWG 100 A · 1 AWG 130 A · 2/0 175 A · 3/0 200 A · 4/0 230 A · 500 kcmil 380 A.

Ampacity in amps — insulated conductors, 0–2000 V, not more than three current-carrying conductors, 30°C ambient
CopperAluminum or copper-clad aluminum
Size60°C75°C90°C60°C75°C90°C
18 AWG14
16 AWG18
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1000 kcmil455545615375445500
1250 kcmil495590665405485545
1500 kcmil525625705435520585
1750 kcmil545650735455545615
2000 kcmil555665750470560630
Small-conductor limit: overcurrent protection is capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper; 15 A for 12 AWG and 25 A for 10 AWG aluminum.
Which insulation types use which column
ColumnConductor types
60°C (140°F)TW, UF
75°C (167°F)RHW, THHW, THW, THWN, XHHW, USE, ZW
90°C (194°F)TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2

Ampacity & derating calculator

Loading calculator…

Ambient above 30°C or more than three loaded conductors? See the derating tables.

Frequently asked questions

Which ampacity column should I use — 60, 75 or 90°C?

Use the column for the lowest-rated part of the circuit. Breakers, panels and most equipment are rated 75°C, so 75°C is the normal answer. Equipment rated 100 A or less, or marked for 14–1 AWG, is treated as 60°C unless it is marked 75°C. NM-B cable is limited to the 60°C column by 334.80. The 90°C column is used only as the starting point for derating.

What is the ampacity of 12 gauge wire?

12 AWG copper is 20 A at 60°C, 25 A at 75°C and 30 A at 90°C, but 240.4(D) limits its overcurrent protection to 20 A in almost all cases. 12 AWG aluminum is 15, 20 and 25 A with a 15 A limit.

Is Table 310.16 the same as 310.15(B)(16)?

Yes. It was Table 310.16 through the 2008 NEC, became 310.15(B)(16) in 2011–2017, and returned to 310.16 in the 2020 edition. The ampacity values are identical.

What conditions does Table 310.16 assume?

Conductors rated up to 2000 V, no more than three current-carrying conductors in a raceway, cable or direct-buried, and an ambient temperature of 30°C (86°F). Anything else needs the correction and adjustment factors.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.