PVC Schedule 40 Conduit Fill Chart

Rigid PVC Conduit, Schedule 40 — NEC Article 352. Gray nonmetallic conduit for underground runs, slabs and wet or corrosive locations. Needs a separate equipment grounding conductor, which counts toward fill.

1/2-inch PVC Schedule 40 holds 8 #12 THHN conductors; 3/4-inch holds 15. Counts assume 40% fill with all conductors the same size.

PVC Schedule 40 fill calculator

Loading calculator…

PVC Schedule 40 sizes

One page per trade size, with counts for every insulation type side by side.

PVC Schedule 40 fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in PVC Schedule 40 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG11213460821351932994015178151178
12 AWG81525435999141218293377594859
10 AWG591527376289137184238374541
8 AWG3591621365179106137216312
6 AWG14611152637577799156225
4 AWG11479162235476196138
3 AWG11368131930405181117
2 AWG1135711162533436898
1 AWG11358121825325073
1/0 AWG11347101521274261
2/0 AWG1123681317223551
3/0 AWG1113571114182942
4/0 AWG11146912152435
250 kcmil11134710122028
300 kcmil113468111724
350 kcmil11135791521
400 kcmil11135681319
500 kcmil11124571116
600 kcmil111345913
700 kcmil111345811
750 kcmil111234711
800 kcmil11234710
900 kcmil1113469
1000 kcmil1113368

PVC Schedule 40 fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in PVC Schedule 40 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG81424425794135209280361568822
12 AWG61118324472103160215277436631
10 AWG481324325477119160206325470
8 AWG247131830436689115181261
6 AWG13510132232496685134193
4 AWG11479162335486197140
3 AWG11368131930405282118
2 AWG1135711162534446999
1 AWG11358121925325174
1/0 AWG11347101621274362
2/0 AWG1123681317233652
3/0 AWG1113571114193043
4/0 AWG11146912152435
250 kcmil11135710132029
300 kcmil113468111725
350 kcmil11135791522
400 kcmil11135681319
500 kcmil11124571116
600 kcmil111345913
700 kcmil111345811
750 kcmil11234711
800 kcmil11234710
900 kcmil1113469
1000 kcmil1113368

PVC Schedule 40 fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in PVC Schedule 40 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG81424425794135209280361568822
12 AWG61118324472103160215277436631
10 AWG481324325477119160206325470
8 AWG247131830436689115181261
6 AWG1248111826405369109157
4 AWG11368131930405181117
3 AWG11357111625344469100
2 AWG1114610142229375985
1 AWG11347101520264160
1/0 AWG1123681317223551
2/0 AWG1113571115193043
3/0 AWG11146912162536
4/0 AWG11135810132130
250 kcmil113468111725
300 kcmil11135791521
350 kcmil11135681319
400 kcmil11134671217
500 kcmil1113561014
600 kcmil111345811
700 kcmil11234710
750 kcmil11134610
800 kcmil1113469
900 kcmil1113368
1000 kcmil1112357

PVC Schedule 40 fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in PVC Schedule 40 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG47112027456499133171269390
12 AWG3591622375382110142224323
10 AWG247131830436689115181261
8 AWG11479152235466094137
6 AWG11357121828374876109
4 AWG1114610142229375985
3 AWG11458121925335275
2 AWG11347101622284565
1 AWG1113571114192943
1/0 AWG11246913162637
2/0 AWG11135811142232
3/0 AWG1113479121928
4/0 AWG112468101624
250 kcmil11134681218
300 kcmil11124571116
350 kcmil1113561014
400 kcmil111346913
500 kcmil111345811
600 kcmil1113469
700 kcmil1113368
750 kcmil1112358
800 kcmil1112357
900 kcmil1111357
1000 kcmil111346

PVC Schedule 40 internal diameter and area

PVC Schedule 40 internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
1/2"160.6020.2850.1510.0880.1140.171
3/4"210.8040.5080.2690.1570.2030.305
1"271.0290.8320.4410.2580.3330.499
1-1/4"351.3601.4530.7700.4500.5810.872
1-1/2"411.5901.9861.0530.6160.7941.192
2"532.0473.2911.7441.0201.3161.975
2-1/2"632.4454.6952.4881.4551.8782.817
3"783.0427.2683.8522.2532.9074.361
3-1/2"913.5219.7375.1613.0183.8955.842
4"1033.99812.5546.6543.8925.0227.532
5"1295.01619.76110.4736.1267.90411.857
6"1556.03128.56715.1418.85611.42717.140

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch PVC Schedule 40?

8 conductors of 12 AWG THHN/THWN-2, or 6 of the thicker THW. In 3/4-inch PVC Schedule 40 the count rises to 15 THHN.

How many #10 wires fit in 1/2-inch PVC Schedule 40?

5 conductors of 10 AWG THHN in 1/2-inch, and 9 in 3/4-inch.

What is the inside diameter of 3/4-inch PVC Schedule 40?

0.804 inches, giving a total internal area of 0.508 in² and 0.203 in² of usable area at 40% fill.

What is the largest wire that fits in 6-inch PVC Schedule 40?

6-inch PVC Schedule 40 holds 16 conductors of 500 kcmil THHN or 8 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.