NEC Table 430.249 — Two-Phase AC Motors (4-Wire) Full-Load Current

Two-phase, 4-wire induction motors. Rare today; current in the common conductor of a 3-wire system is 1.41 times the value shown.

A 10 HP two-phase motor draws 12 A at 460 V, and a 125 HP motor draws 108 A at 575 V. Use these values, not the nameplate, to size conductors and short-circuit protection.

Full-load current in amps — two-phase ac motors (4-wire)
Horsepower115 V230 V460 V575 V2300 V
1/2 HP4210.8
3/4 HP4.82.41.21
1 HP6.43.21.61.3
1 1/2 HP94.52.31.8
2 HP11.85.932.4
3 HP8.34.23.3
5 HP13.26.65.3
7 1/2 HP1998
10 HP241210
15 HP361814
20 HP472319
25 HP592924
30 HP693528
40 HP904536
50 HP1135645
60 HP133675314
75 HP166836618
100 HP2181098723
125 HP27013510828
150 HP31215612532
200 HP41620816743

Frequently asked questions

How many amps does a 10 HP two-phase ac motor draw?

A 10 HP two-phase motor draws 12 A at 460 V. 24 A at 230 V, 12 A at 460 V, 10 A at 575 V.

Should I use the nameplate amps or the table amps?

Use the table full-load current for sizing branch-circuit conductors, the short-circuit and ground-fault protective device, and the disconnect (430.6(A)(1)). Use the motor nameplate current only for sizing the separate overload protection.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.