5 HP Motor Amps — Full-Load Current, Wire & Breaker Size
Full-load current of a 5 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.
A 5 HP motor draws 15.2 A at 230 V and 7.6 A at 460 V three-phase; 56 A at 115 V and 28 A at 230 V single-phase.
5 HP three-phase motor
| Voltage | Full-load amps | Conductor ampacity (125%) | Min. copper wire, 75°C | Max. inverse-time breaker (250%) | Max. time-delay fuse (175%) |
|---|---|---|---|---|---|
| 200 V | 17.5 A | 21.9 A | 12 AWG | 45 A | 35 A |
| 208 V | 16.7 A | 20.9 A | 12 AWG | 45 A | 30 A |
| 230 V | 15.2 A | 19.0 A | 14 AWG | 40 A | 30 A |
| 460 V | 7.6 A | 9.5 A | 14 AWG | 20 A | 15 A |
| 575 V | 6.1 A | 7.6 A | 14 AWG | 20 A | 15 A |
5 HP single-phase motor
| Voltage | Full-load amps | Conductor ampacity (125%) | Min. copper wire, 75°C | Max. inverse-time breaker (250%) | Max. time-delay fuse (175%) |
|---|---|---|---|---|---|
| 115 V | 56 A | 70.0 A | 4 AWG | 150 A | 100 A |
| 200 V | 32.2 A | 40.2 A | 8 AWG | 90 A | 60 A |
| 208 V | 30.8 A | 38.5 A | 8 AWG | 80 A | 60 A |
| 230 V | 28 A | 35.0 A | 10 AWG | 70 A | 50 A |
5 HP DC motor
| Armature voltage | Full-load amps | Conductor ampacity (125%) |
|---|---|---|
| 120 V | 40 A | 50.0 A |
| 180 V | 27 A | 33.8 A |
| 240 V | 20 A | 25.0 A |
5 HP two-phase motor
| Voltage | Full-load amps |
|---|---|
| 230 V | 13.2 A |
| 460 V | 6.6 A |
| 575 V | 5.3 A |
5 HP is 3.73 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.
Motor wire & breaker size calculator
Loading calculator…
Other horsepower ratings
- 1/6 HP
- 1/4 HP
- 1/3 HP
- 1/2 HP
- 3/4 HP
- 1 HP
- 1 1/2 HP
- 2 HP
- 3 HP
- 5 HP
- 7 1/2 HP
- 10 HP
- 15 HP
- 20 HP
- 25 HP
- 30 HP
- 40 HP
- 50 HP
- 60 HP
- 75 HP
- 100 HP
- 125 HP
- 150 HP
- 200 HP
- 250 HP
- 300 HP
- 350 HP
- 400 HP
- 450 HP
- 500 HP
Frequently asked questions
How many amps does a 5 HP motor draw?
A 5 HP motor draws 15.2 A at 230 V and 7.6 A at 460 V three-phase; 56 A at 115 V and 28 A at 230 V single-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.
What size wire and breaker for a 5 HP three-phase motor at 460 V?
Full-load current is 7.6 A, so conductors need at least 9.5 A of ampacity: 14 AWG copper at 75°C. The inverse-time breaker may be up to 20 A and a dual-element time-delay fuse up to 15 A.
What size wire for a 5 HP single-phase motor at 230 V?
28 A × 125% = 35.0 A, so 10 AWG copper is the minimum, with a breaker no larger than 70 A. At 115 V the current doubles to 56 A.
NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.