10 AWG Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 10 AWG conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

10 AWG copper carries 30 A at 60°C, 35 A at 75°C and 40 A at 90°C. Overcurrent protection is capped at 30 A for copper and 25 A for aluminum by the small-conductor rule in 240.4(D), whatever the ampacity column says.

Copper, 75°C
35 A
Aluminum, 75°C
30 A
Conductor area
10,380 cmil · 5.26 mm²
THHN diameter
0.164 in
DC resistance, Cu
1.24 Ω/1000 ft

10 AWG ampacity

10 AWG ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16303540253035
Single conductor in free air — Table 310.17405055354045

Typical use: 30 A circuits: electric dryers, water heaters, air-conditioner condensers, and long 20 A runs upsized for voltage drop.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 10 AWG is the minimum for circuits protected at up to 60 A; in aluminum, up to 20 A. See the grounding conductor table.

10 AWG conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

10 AWG dimensions

10 AWG overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-20.1644.170.021113.6
XHHW, XHHW-2, XHH0.1764.470.024315.7
TW, THW, THHW, THW-20.1764.470.024315.7
RHH, RHW, RHW-2 (with outer covering)0.2365.990.043728.2

10 AWG voltage drop

Maximum one-way length of 10 AWG copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
5 A290 ft580 ft581 ft1340 ft
10 A145 ft290 ft290 ft670 ft
15 A96 ft193 ft193 ft446 ft
20 A72 ft145 ft145 ft335 ft
30 A48 ft96 ft96 ft223 ft

Based on 1.24 Ω per 1000 ft for stranded copper at 75°C (2.04 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 10 AWG wire carry?

10 AWG copper is rated 30 A at 60°C, 35 A at 75°C and 40 A at 90°C when run in conduit or cable. Aluminum is rated 25, 30 and 35 A. Breaker size is limited to 30 A for copper.

What size conduit do I need for 10 AWG wire?

Three 10 AWG THHN conductors need at least 1/2-inch EMT. 1/2-inch EMT holds 5 and 3/4-inch holds 10.

What is the diameter of 10 AWG wire?

The bare conductor is 10,380 circular mils (5.26 mm²). With THHN insulation the overall diameter is about 0.164 in (4.17 mm) and the area is 0.0211 in², which is the figure used for conduit fill.

How far can I run 10 AWG wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 30 A, about 96 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.