800 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 800 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

800 kcmil copper carries 410 A at 60°C, 490 A at 75°C and 555 A at 90°C.

Copper, 75°C
490 A
Aluminum, 75°C
395 A
Conductor area
800,000 cmil · 405.36 mm²
THHN diameter
1.188 in
DC resistance, Cu
0.0161 Ω/1000 ft

800 kcmil ampacity

800 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16410490555330395445
Single conductor in free air — Table 310.17680815920535645725

Typical use: 490 A copper. Rare in practice.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 800 kcmil is the minimum for circuits protected at up to 6000 A. See the grounding conductor table.

800 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

800 kcmil dimensions

800 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-21.18830.181.1085715.2
XHHW, XHHW-2, XHH1.19030.231.1122717.5
TW, THW, THHW, THW-21.25031.751.2272791.7
RHH, RHW, RHW-2 (with outer covering)1.38035.051.4957965.0

800 kcmil voltage drop

Maximum one-way length of 800 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
150 A745 ft1490 ft1491 ft3442 ft
200 A559 ft1118 ft1118 ft2581 ft
250 A447 ft894 ft895 ft2065 ft
300 A372 ft745 ft745 ft1721 ft
400 A279 ft559 ft559 ft1290 ft

Based on 0.0161 Ω per 1000 ft for stranded copper at 75°C (0.0265 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 800 kcmil wire carry?

800 kcmil copper is rated 410 A at 60°C, 490 A at 75°C and 555 A at 90°C when run in conduit or cable. Aluminum is rated 330, 395 and 445 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 800 kcmil wire?

Three 800 kcmil THHN conductors need at least 3-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 800 kcmil wire?

The bare conductor is 800,000 circular mils (405.36 mm²). With THHN insulation the overall diameter is about 1.188 in (30.18 mm) and the area is 1.1085 in², which is the figure used for conduit fill.

How far can I run 800 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 400 A, about 559 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.