600 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 600 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

600 kcmil copper carries 350 A at 60°C, 420 A at 75°C and 475 A at 90°C.

Copper, 75°C
420 A
Aluminum, 75°C
340 A
Conductor area
600,000 cmil · 304.02 mm²
THHN diameter
1.051 in
DC resistance, Cu
0.0214 Ω/1000 ft

600 kcmil ampacity

600 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16350420475285340385
Single conductor in free air — Table 310.17575690780455545615

Typical use: 420 A copper; parallel 600 kcmil sets are typical for 1200–1600 A gear.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

600 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

600 kcmil dimensions

600 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-21.05126.700.8676559.7
XHHW, XHHW-2, XHH1.05326.750.8709561.9
TW, THW, THHW, THW-21.11328.270.9729627.7
RHH, RHW, RHW-2 (with outer covering)1.24331.571.2135782.9

600 kcmil voltage drop

Maximum one-way length of 600 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
150 A560 ft1121 ft1122 ft2589 ft
200 A420 ft841 ft841 ft1942 ft
250 A336 ft672 ft673 ft1553 ft
300 A280 ft560 ft561 ft1294 ft
400 A210 ft420 ft420 ft971 ft

Based on 0.0214 Ω per 1000 ft for stranded copper at 75°C (0.0353 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 600 kcmil wire carry?

600 kcmil copper is rated 350 A at 60°C, 420 A at 75°C and 475 A at 90°C when run in conduit or cable. Aluminum is rated 285, 340 and 385 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 600 kcmil wire?

Three 600 kcmil THHN conductors need at least 3-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 600 kcmil wire?

The bare conductor is 600,000 circular mils (304.02 mm²). With THHN insulation the overall diameter is about 1.051 in (26.70 mm) and the area is 0.8676 in², which is the figure used for conduit fill.

How far can I run 600 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 400 A, about 420 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.