3 AWG Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 3 AWG conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

3 AWG copper carries 85 A at 60°C, 100 A at 75°C and 115 A at 90°C.

Copper, 75°C
100 A
Aluminum, 75°C
75 A
Conductor area
52,620 cmil · 26.66 mm²
THHN diameter
0.352 in
DC resistance, Cu
0.245 Ω/1000 ft

3 AWG ampacity

3 AWG ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.1685100115657585
Single conductor in free air — Table 310.1712014516595115130

Typical use: 100 A feeders in copper at 75°C terminations.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 3 AWG is the minimum for circuits protected at up to 400 A. See the grounding conductor table.

3 AWG conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

3 AWG dimensions

3 AWG overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-20.3528.940.097362.8
XHHW, XHHW-2, XHH0.3508.890.096262.1
TW, THW, THHW, THW-20.3809.650.113473.2
RHH, RHW, RHW-2 (with outer covering)0.44011.180.152198.1

3 AWG voltage drop

Maximum one-way length of 3 AWG copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
40 A183 ft367 ft367 ft848 ft
50 A146 ft293 ft294 ft678 ft
60 A122 ft244 ft245 ft565 ft
80 A91 ft183 ft183 ft424 ft
100 A73 ft146 ft147 ft339 ft

Based on 0.245 Ω per 1000 ft for stranded copper at 75°C (0.403 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 3 AWG wire carry?

3 AWG copper is rated 85 A at 60°C, 100 A at 75°C and 115 A at 90°C when run in conduit or cable. Aluminum is rated 65, 75 and 85 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 3 AWG wire?

Three 3 AWG THHN conductors need at least 1-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 3 AWG wire?

The bare conductor is 52,620 circular mils (26.66 mm²). With THHN insulation the overall diameter is about 0.352 in (8.94 mm) and the area is 0.0973 in², which is the figure used for conduit fill.

How far can I run 3 AWG wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 100 A, about 146 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.