700 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 700 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

700 kcmil copper carries 385 A at 60°C, 460 A at 75°C and 520 A at 90°C.

Copper, 75°C
460 A
Aluminum, 75°C
375 A
Conductor area
700,000 cmil · 354.69 mm²
THHN diameter
1.122 in
DC resistance, Cu
0.0184 Ω/1000 ft

700 kcmil ampacity

700 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16385460520315375425
Single conductor in free air — Table 310.17630755850500595670

Typical use: 460 A copper. Uncommon; most designs jump from 600 to 750 kcmil.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 700 kcmil is the minimum for circuits protected at up to 5000 A. See the grounding conductor table.

700 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

700 kcmil dimensions

700 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-21.12228.500.9887637.9
XHHW, XHHW-2, XHH1.12428.550.9923640.2
TW, THW, THHW, THW-21.18430.071.1010710.3
RHH, RHW, RHW-2 (with outer covering)1.31433.381.3561874.9

700 kcmil voltage drop

Maximum one-way length of 700 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
150 A652 ft1304 ft1305 ft3012 ft
200 A489 ft978 ft978 ft2259 ft
250 A391 ft782 ft783 ft1807 ft
300 A326 ft652 ft652 ft1506 ft
400 A244 ft489 ft489 ft1129 ft

Based on 0.0184 Ω per 1000 ft for stranded copper at 75°C (0.0303 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 700 kcmil wire carry?

700 kcmil copper is rated 385 A at 60°C, 460 A at 75°C and 520 A at 90°C when run in conduit or cable. Aluminum is rated 315, 375 and 425 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 700 kcmil wire?

Three 700 kcmil THHN conductors need at least 3-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 700 kcmil wire?

The bare conductor is 700,000 circular mils (354.69 mm²). With THHN insulation the overall diameter is about 1.122 in (28.50 mm) and the area is 0.9887 in², which is the figure used for conduit fill.

How far can I run 700 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 400 A, about 489 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.