250 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 250 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

250 kcmil copper carries 215 A at 60°C, 255 A at 75°C and 290 A at 90°C.

Copper, 75°C
255 A
Aluminum, 75°C
205 A
Conductor area
250,000 cmil · 126.67 mm²
THHN diameter
0.711 in
DC resistance, Cu
0.0515 Ω/1000 ft

250 kcmil ampacity

250 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16215255290170205230
Single conductor in free air — Table 310.17340405455265315355

Typical use: 250 A copper feeders; 250 kcmil aluminum is common for 225 A panels.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 250 kcmil is the minimum for circuits protected at up to 2000 A; in aluminum, up to 1200 A. See the grounding conductor table.

250 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

250 kcmil dimensions

250 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-20.71118.060.3970256.1
XHHW, XHHW-2, XHH0.70517.910.3904251.9
TW, THW, THHW, THW-20.76519.430.4596296.5
RHH, RHW, RHW-2 (with outer covering)0.89522.730.6291405.9

250 kcmil voltage drop

Maximum one-way length of 250 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
100 A349 ft699 ft699 ft1614 ft
125 A279 ft559 ft559 ft1291 ft
150 A233 ft466 ft466 ft1076 ft
200 A174 ft349 ft349 ft807 ft
250 A139 ft279 ft279 ft645 ft

Based on 0.0515 Ω per 1000 ft for stranded copper at 75°C (0.0847 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 250 kcmil wire carry?

250 kcmil copper is rated 215 A at 60°C, 255 A at 75°C and 290 A at 90°C when run in conduit or cable. Aluminum is rated 170, 205 and 230 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 250 kcmil wire?

Three 250 kcmil THHN conductors need at least 2-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 250 kcmil wire?

The bare conductor is 250,000 circular mils (126.67 mm²). With THHN insulation the overall diameter is about 0.711 in (18.06 mm) and the area is 0.3970 in², which is the figure used for conduit fill.

How far can I run 250 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 250 A, about 279 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.