500 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 500 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

500 kcmil copper carries 320 A at 60°C, 380 A at 75°C and 430 A at 90°C.

Copper, 75°C
380 A
Aluminum, 75°C
310 A
Conductor area
500,000 cmil · 253.35 mm²
THHN diameter
0.949 in
DC resistance, Cu
0.0258 Ω/1000 ft

500 kcmil ampacity

500 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16320380430260310350
Single conductor in free air — Table 310.17515620700405485545

Typical use: 380 A copper. The workhorse of large feeders; parallel 500s build 800–2000 A services.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 500 kcmil is the minimum for circuits protected at up to 4000 A. See the grounding conductor table.

500 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

500 kcmil dimensions

500 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-20.94924.100.7073456.3
XHHW, XHHW-2, XHH0.94323.950.6984450.6
TW, THW, THHW, THW-21.00325.480.7901509.7
RHH, RHW, RHW-2 (with outer covering)1.13328.781.0082650.5

500 kcmil voltage drop

Maximum one-way length of 500 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
125 A558 ft1116 ft1117 ft2577 ft
150 A465 ft930 ft930 ft2148 ft
200 A348 ft697 ft698 ft1611 ft
250 A279 ft558 ft558 ft1288 ft
300 A232 ft465 ft465 ft1074 ft

Based on 0.0258 Ω per 1000 ft for stranded copper at 75°C (0.0424 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 500 kcmil wire carry?

500 kcmil copper is rated 320 A at 60°C, 380 A at 75°C and 430 A at 90°C when run in conduit or cable. Aluminum is rated 260, 310 and 350 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 500 kcmil wire?

Three 500 kcmil THHN conductors need at least 2-1/2-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 500 kcmil wire?

The bare conductor is 500,000 circular mils (253.35 mm²). With THHN insulation the overall diameter is about 0.949 in (24.10 mm) and the area is 0.7073 in², which is the figure used for conduit fill.

How far can I run 500 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 300 A, about 465 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.