750 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 750 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

750 kcmil copper carries 400 A at 60°C, 475 A at 75°C and 535 A at 90°C.

Copper, 75°C
475 A
Aluminum, 75°C
385 A
Conductor area
750,000 cmil · 380.03 mm²
THHN diameter
1.156 in
DC resistance, Cu
0.0171 Ω/1000 ft

750 kcmil ampacity

750 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16400475535320385435
Single conductor in free air — Table 310.17655785885515620700

Typical use: 475 A copper, 385 A aluminum. Largest size most lugs and benders handle comfortably.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

750 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

750 kcmil dimensions

750 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-21.15629.361.0496677.2
XHHW, XHHW-2, XHH1.15829.411.0532679.5
TW, THW, THHW, THW-21.21830.941.1652751.7
RHH, RHW, RHW-2 (with outer covering)1.34834.241.4272920.8

750 kcmil voltage drop

Maximum one-way length of 750 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
150 A701 ft1403 ft1404 ft3241 ft
200 A526 ft1052 ft1053 ft2430 ft
250 A421 ft842 ft842 ft1944 ft
300 A350 ft701 ft702 ft1620 ft
400 A263 ft526 ft526 ft1215 ft

Based on 0.0171 Ω per 1000 ft for stranded copper at 75°C (0.0282 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 750 kcmil wire carry?

750 kcmil copper is rated 400 A at 60°C, 475 A at 75°C and 535 A at 90°C when run in conduit or cable. Aluminum is rated 320, 385 and 435 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 750 kcmil wire?

Three 750 kcmil THHN conductors need at least 3-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 750 kcmil wire?

The bare conductor is 750,000 circular mils (380.03 mm²). With THHN insulation the overall diameter is about 1.156 in (29.36 mm) and the area is 1.0496 in², which is the figure used for conduit fill.

How far can I run 750 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 400 A, about 526 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.