400 kcmil Wire — Ampacity, Conduit Fill & Dimensions

Everything the code tables say about 400 kcmil conductors on one page: ampacity by temperature rating, breaker limits, conduit fill, physical size, resistance and voltage-drop distances.

400 kcmil copper carries 280 A at 60°C, 335 A at 75°C and 380 A at 90°C.

Copper, 75°C
335 A
Aluminum, 75°C
270 A
Conductor area
400,000 cmil · 202.68 mm²
THHN diameter
0.864 in
DC resistance, Cu
0.0321 Ω/1000 ft

400 kcmil ampacity

400 kcmil ampacity (amps), 30°C ambient, not more than three current-carrying conductors
CopperAluminum
Installation60°C75°C90°C60°C75°C90°C
Raceway, cable or earth — Table 310.16280335380225270305
Single conductor in free air — Table 310.17455545615355425480

Typical use: 335 A copper; 400 A services are normally built from parallel sets or 500–600 kcmil.

Use the column that matches the lowest temperature rating in the circuit — usually the 75°C terminations on breakers and lugs. The 90°C column is a starting point for derating, not a rating you can load the wire to. NM-B (Romex) cable is always limited to the 60°C column.

As a copper equipment grounding conductor, 400 kcmil is the minimum for circuits protected at up to 3000 A; in aluminum, up to 2000 A. See the grounding conductor table.

400 kcmil conduit fill

Mixing sizes or using another insulation? Use the conduit fill calculator.

400 kcmil dimensions

400 kcmil overall diameter and area including insulation
InsulationDiameter (in)Diameter (mm)Area (in²)Area (mm²)
THHN, THWN, THWN-20.86421.950.5863378.3
XHHW, XHHW-2, XHH0.85821.790.5782373.0
TW, THW, THHW, THW-20.91823.320.6619427.0
RHH, RHW, RHW-2 (with outer covering)1.04826.620.8626556.5

400 kcmil voltage drop

Maximum one-way length of 400 kcmil copper for 3% voltage drop
Load120 V 1-phase240 V 1-phase208 V 3-phase480 V 3-phase
125 A448 ft897 ft897 ft2071 ft
150 A373 ft747 ft748 ft1726 ft
200 A280 ft560 ft561 ft1294 ft
250 A224 ft448 ft448 ft1035 ft
300 A186 ft373 ft374 ft863 ft

Based on 0.0321 Ω per 1000 ft for stranded copper at 75°C (0.0529 Ω for aluminum). For other loads and lengths use the voltage drop calculator.

All wire sizes

Frequently asked questions

How many amps can 400 kcmil wire carry?

400 kcmil copper is rated 280 A at 60°C, 335 A at 75°C and 380 A at 90°C when run in conduit or cable. Aluminum is rated 225, 270 and 305 A. Most terminations are rated 75°C, so the 75°C figure is the one normally used.

What size conduit do I need for 400 kcmil wire?

Three 400 kcmil THHN conductors need at least 2-1/2-inch EMT. Add the ground wire’s area and check the chart above for larger bundles.

What is the diameter of 400 kcmil wire?

The bare conductor is 400,000 circular mils (202.68 mm²). With THHN insulation the overall diameter is about 0.864 in (21.95 mm) and the area is 0.5863 in², which is the figure used for conduit fill.

How far can I run 400 kcmil wire?

For a 3% voltage drop on a 240 V single-phase circuit carrying 300 A, about 373 feet one way in copper. Halve that at 120 V. Lighter loads go proportionally farther.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.