1/2-inch EMT Conduit Fill

Wire capacity of trade size 1/2 (metric designator 16) Electrical Metallic Tubing, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1/2-inch EMT holds 12 × #14, 9 × #12, 5 × #10 or 3 × #8 THHN conductors at 40% fill. Internal area: 0.304 in²; usable at 40%: 0.122 in².

Internal diameter
0.622 in · 15.8 mm
Total area
0.304 in² · 196 mm²
40% fill (3+ wires)
0.122 in²
31% / 53% (2 / 1 wire)
0.094 / 0.161 in²
Maximum conductors in 1/2-inch EMT
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG12884190.0097
12 AWG9663130.0133
10 AWG555280.0211
8 AWG322150.0366
6 AWG111130.0507
4 AWG111120.0824
3 AWG111120.0973
2 AWG11110.1158
1 AWG1110.1562
1/0 AWG10.1855
2/0 AWG10.2223
3/0 AWG0.2679
4/0 AWG0.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1/2-inch conduit: EMT vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT0.6220.3040.122951
PVC Schedule 400.6020.2850.114851
PVC Schedule 800.5260.2170.087641
Rigid Metal Conduit0.6320.3140.126961
IMC0.6600.3420.1371062
Flexible Metal Conduit0.6350.3170.127961
Liquidtight Flexible Metal Conduit0.6320.3140.126961
ENT0.6020.2850.114851

Other EMT sizes

Frequently asked questions

How many #12 wires fit in 1/2-inch EMT?

9 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 6.

What is the inside diameter and area of 1/2-inch EMT?

The internal diameter is 0.622 in. (15.8 mm) and the total cross-sectional area is 0.304 in². The usable area is 0.122 in² at 40% fill, 0.094 in² for two wires and 0.161 in² for one.

What is the largest wire I can pull three of in 1/2-inch EMT?

8 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.