1-inch EMT Conduit Fill

Wire capacity of trade size 1 (metric designator 27) Electrical Metallic Tubing, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-inch EMT holds 35 × #14, 26 × #12, 16 × #10 or 9 × #8 THHN conductors at 40% fill. Internal area: 0.864 in²; usable at 40%: 0.346 in².

Internal diameter
1.049 in · 26.6 mm
Total area
0.864 in² · 557 mm²
40% fill (3+ wires)
0.346 in²
31% / 53% (2 / 1 wire)
0.268 / 0.458 in²
Maximum conductors in 1-inch EMT
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG35252511530.0097
12 AWG2619199390.0133
10 AWG1614148240.0211
8 AWG9884140.0366
6 AWG7643100.0507
4 AWG443260.0824
3 AWG333150.0973
2 AWG332140.1158
1 AWG111130.1562
1/0 AWG111120.1855
2/0 AWG111120.2223
3/0 AWG111120.2679
4/0 AWG11110.3237
250 kcmil1110.3970
300 kcmil110.4608
350 kcmil10.5242
400 kcmil10.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-inch conduit: EMT vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.0490.8640.34626167
PVC Schedule 401.0290.8320.33325156
PVC Schedule 800.9360.6880.27520135
Rigid Metal Conduit1.0630.8870.35526177
IMC1.1050.9590.38429187
Flexible Metal Conduit1.0200.8170.32724156
Liquidtight Flexible Metal Conduit1.0540.8730.34926167
ENT1.0290.8320.33325156

Other EMT sizes

Frequently asked questions

How many #12 wires fit in 1-inch EMT?

26 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 19.

What is the inside diameter and area of 1-inch EMT?

The internal diameter is 1.049 in. (26.6 mm) and the total cross-sectional area is 0.864 in². The usable area is 0.346 in² at 40% fill, 0.268 in² for two wires and 0.458 in² for one.

What is the largest wire I can pull three of in 1-inch EMT?

2 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 26 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.