400 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 400 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 400 HP motor draws 477 A at 460 V and 382 A at 575 V three-phase.

400 HP three-phase motor

400 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
460 V477 A596.2 A1500 kcmil1200 A1000 A
575 V382 A477.5 A800 kcmil1000 A700 A
2300 V95 A118.8 A1 AWG250 A175 A

400 HP is 298.40 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 400 HP motor draw?

A 400 HP motor draws 477 A at 460 V and 382 A at 575 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 400 HP three-phase motor at 460 V?

Full-load current is 477 A, so conductors need at least 596.2 A of ampacity: 1500 kcmil copper at 75°C. The inverse-time breaker may be up to 1200 A and a dual-element time-delay fuse up to 1000 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.