75 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 75 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 75 HP motor draws 192 A at 230 V and 96 A at 460 V three-phase.

75 HP three-phase motor

75 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V221 A276.2 A300 kcmil600 A400 A
208 V211 A263.8 A300 kcmil600 A400 A
230 V192 A240.0 A250 kcmil500 A350 A
460 V96 A120.0 A1 AWG250 A175 A
575 V77 A96.2 A3 AWG200 A150 A
2300 V20 A25.0 A12 AWG50 A35 A

75 HP DC motor

75 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
240 V255 A318.8 A
500 V123 A153.8 A
550 V111 A138.8 A

75 HP two-phase motor

75 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V166 A
460 V83 A
575 V66 A
2300 V18 A

75 HP is 55.95 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 75 HP motor draw?

A 75 HP motor draws 192 A at 230 V and 96 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 75 HP three-phase motor at 460 V?

Full-load current is 96 A, so conductors need at least 120.0 A of ampacity: 1 AWG copper at 75°C. The inverse-time breaker may be up to 250 A and a dual-element time-delay fuse up to 175 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.