75 HP Motor Amps — Full-Load Current, Wire & Breaker Size
Full-load current of a 75 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.
A 75 HP motor draws 192 A at 230 V and 96 A at 460 V three-phase.
75 HP three-phase motor
| Voltage | Full-load amps | Conductor ampacity (125%) | Min. copper wire, 75°C | Max. inverse-time breaker (250%) | Max. time-delay fuse (175%) |
|---|---|---|---|---|---|
| 200 V | 221 A | 276.2 A | 300 kcmil | 600 A | 400 A |
| 208 V | 211 A | 263.8 A | 300 kcmil | 600 A | 400 A |
| 230 V | 192 A | 240.0 A | 250 kcmil | 500 A | 350 A |
| 460 V | 96 A | 120.0 A | 1 AWG | 250 A | 175 A |
| 575 V | 77 A | 96.2 A | 3 AWG | 200 A | 150 A |
| 2300 V | 20 A | 25.0 A | 12 AWG | 50 A | 35 A |
75 HP DC motor
| Armature voltage | Full-load amps | Conductor ampacity (125%) |
|---|---|---|
| 240 V | 255 A | 318.8 A |
| 500 V | 123 A | 153.8 A |
| 550 V | 111 A | 138.8 A |
75 HP two-phase motor
| Voltage | Full-load amps |
|---|---|
| 230 V | 166 A |
| 460 V | 83 A |
| 575 V | 66 A |
| 2300 V | 18 A |
75 HP is 55.95 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.
Motor wire & breaker size calculator
Loading calculator…
Other horsepower ratings
- 1/6 HP
- 1/4 HP
- 1/3 HP
- 1/2 HP
- 3/4 HP
- 1 HP
- 1 1/2 HP
- 2 HP
- 3 HP
- 5 HP
- 7 1/2 HP
- 10 HP
- 15 HP
- 20 HP
- 25 HP
- 30 HP
- 40 HP
- 50 HP
- 60 HP
- 75 HP
- 100 HP
- 125 HP
- 150 HP
- 200 HP
- 250 HP
- 300 HP
- 350 HP
- 400 HP
- 450 HP
- 500 HP
Frequently asked questions
How many amps does a 75 HP motor draw?
A 75 HP motor draws 192 A at 230 V and 96 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.
What size wire and breaker for a 75 HP three-phase motor at 460 V?
Full-load current is 96 A, so conductors need at least 120.0 A of ampacity: 1 AWG copper at 75°C. The inverse-time breaker may be up to 250 A and a dual-element time-delay fuse up to 175 A.
NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.