250 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 250 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 250 HP motor draws 302 A at 460 V and 242 A at 575 V three-phase.

250 HP three-phase motor

250 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
460 V302 A377.5 A500 kcmil800 A600 A
575 V242 A302.5 A350 kcmil700 A450 A
2300 V60 A75.0 A4 AWG150 A110 A

250 HP is 186.50 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 250 HP motor draw?

A 250 HP motor draws 302 A at 460 V and 242 A at 575 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 250 HP three-phase motor at 460 V?

Full-load current is 302 A, so conductors need at least 377.5 A of ampacity: 500 kcmil copper at 75°C. The inverse-time breaker may be up to 800 A and a dual-element time-delay fuse up to 600 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.