500 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 500 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 500 HP motor draws 590 A at 460 V and 472 A at 575 V three-phase.

500 HP three-phase motor

500 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
460 V590 A737.5 Aparallel1600 A1200 A
575 V472 A590.0 A1250 kcmil1200 A1000 A
2300 V118 A147.5 A1/0 AWG300 A225 A

500 HP is 373.00 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 500 HP motor draw?

A 500 HP motor draws 590 A at 460 V and 472 A at 575 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 500 HP three-phase motor at 460 V?

Full-load current is 590 A, so conductors need at least 737.5 A of ampacity: parallel sets of copper at 75°C. The inverse-time breaker may be up to 1600 A and a dual-element time-delay fuse up to 1200 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.