25 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 25 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 25 HP motor draws 68 A at 230 V and 34 A at 460 V three-phase.

25 HP three-phase motor

25 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V78.2 A97.8 A3 AWG200 A150 A
208 V74.8 A93.5 A3 AWG200 A150 A
230 V68 A85.0 A4 AWG175 A125 A
460 V34 A42.5 A8 AWG90 A60 A
575 V27 A33.8 A10 AWG70 A50 A

25 HP DC motor

25 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
240 V89 A111.2 A
500 V43 A53.8 A
550 V38 A47.5 A

25 HP two-phase motor

25 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V59 A
460 V29 A
575 V24 A

25 HP is 18.65 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 25 HP motor draw?

A 25 HP motor draws 68 A at 230 V and 34 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 25 HP three-phase motor at 460 V?

Full-load current is 34 A, so conductors need at least 42.5 A of ampacity: 8 AWG copper at 75°C. The inverse-time breaker may be up to 90 A and a dual-element time-delay fuse up to 60 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.