125 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 125 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 125 HP motor draws 312 A at 230 V and 156 A at 460 V three-phase.

125 HP three-phase motor

125 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V359 A448.8 A700 kcmil1000 A700 A
208 V343 A428.8 A700 kcmil1000 A700 A
230 V312 A390.0 A600 kcmil800 A600 A
460 V156 A195.0 A3/0 AWG400 A300 A
575 V125 A156.2 A2/0 AWG350 A225 A
2300 V31 A38.8 A8 AWG80 A60 A

125 HP DC motor

125 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
240 V425 A531.2 A
500 V205 A256.2 A
550 V185 A231.2 A

125 HP two-phase motor

125 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V270 A
460 V135 A
575 V108 A
2300 V28 A

125 HP is 93.25 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 125 HP motor draw?

A 125 HP motor draws 312 A at 230 V and 156 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 125 HP three-phase motor at 460 V?

Full-load current is 156 A, so conductors need at least 195.0 A of ampacity: 3/0 AWG copper at 75°C. The inverse-time breaker may be up to 400 A and a dual-element time-delay fuse up to 300 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.