125 HP Motor Amps — Full-Load Current, Wire & Breaker Size
Full-load current of a 125 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.
A 125 HP motor draws 312 A at 230 V and 156 A at 460 V three-phase.
125 HP three-phase motor
| Voltage | Full-load amps | Conductor ampacity (125%) | Min. copper wire, 75°C | Max. inverse-time breaker (250%) | Max. time-delay fuse (175%) |
|---|---|---|---|---|---|
| 200 V | 359 A | 448.8 A | 700 kcmil | 1000 A | 700 A |
| 208 V | 343 A | 428.8 A | 700 kcmil | 1000 A | 700 A |
| 230 V | 312 A | 390.0 A | 600 kcmil | 800 A | 600 A |
| 460 V | 156 A | 195.0 A | 3/0 AWG | 400 A | 300 A |
| 575 V | 125 A | 156.2 A | 2/0 AWG | 350 A | 225 A |
| 2300 V | 31 A | 38.8 A | 8 AWG | 80 A | 60 A |
125 HP DC motor
| Armature voltage | Full-load amps | Conductor ampacity (125%) |
|---|---|---|
| 240 V | 425 A | 531.2 A |
| 500 V | 205 A | 256.2 A |
| 550 V | 185 A | 231.2 A |
125 HP two-phase motor
| Voltage | Full-load amps |
|---|---|
| 230 V | 270 A |
| 460 V | 135 A |
| 575 V | 108 A |
| 2300 V | 28 A |
125 HP is 93.25 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.
Motor wire & breaker size calculator
Loading calculator…
Other horsepower ratings
- 1/6 HP
- 1/4 HP
- 1/3 HP
- 1/2 HP
- 3/4 HP
- 1 HP
- 1 1/2 HP
- 2 HP
- 3 HP
- 5 HP
- 7 1/2 HP
- 10 HP
- 15 HP
- 20 HP
- 25 HP
- 30 HP
- 40 HP
- 50 HP
- 60 HP
- 75 HP
- 100 HP
- 125 HP
- 150 HP
- 200 HP
- 250 HP
- 300 HP
- 350 HP
- 400 HP
- 450 HP
- 500 HP
Frequently asked questions
How many amps does a 125 HP motor draw?
A 125 HP motor draws 312 A at 230 V and 156 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.
What size wire and breaker for a 125 HP three-phase motor at 460 V?
Full-load current is 156 A, so conductors need at least 195.0 A of ampacity: 3/0 AWG copper at 75°C. The inverse-time breaker may be up to 400 A and a dual-element time-delay fuse up to 300 A.
NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.