200 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 200 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 200 HP motor draws 480 A at 230 V and 240 A at 460 V three-phase.

200 HP three-phase motor

200 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V552 A690.0 Aparallel1600 A1000 A
208 V528 A660.0 A2000 kcmil1600 A1000 A
230 V480 A600.0 A1500 kcmil1200 A1000 A
460 V240 A300.0 A350 kcmil600 A450 A
575 V192 A240.0 A250 kcmil500 A350 A
2300 V49 A61.2 A6 AWG125 A90 A

200 HP DC motor

200 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
240 V675 A843.8 A
500 V330 A412.5 A
550 V294 A367.5 A

200 HP two-phase motor

200 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V416 A
460 V208 A
575 V167 A
2300 V43 A

200 HP is 149.20 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 200 HP motor draw?

A 200 HP motor draws 480 A at 230 V and 240 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 200 HP three-phase motor at 460 V?

Full-load current is 240 A, so conductors need at least 300.0 A of ampacity: 350 kcmil copper at 75°C. The inverse-time breaker may be up to 600 A and a dual-element time-delay fuse up to 450 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.