50 HP Motor Amps — Full-Load Current, Wire & Breaker Size

Full-load current of a 50 horsepower motor at every standard voltage, with minimum conductor size and maximum breaker and fuse ratings worked out for each.

A 50 HP motor draws 130 A at 230 V and 65 A at 460 V three-phase.

50 HP three-phase motor

50 HP three-phase induction motor — current and circuit sizing
VoltageFull-load ampsConductor ampacity (125%)Min. copper wire, 75°CMax. inverse-time breaker (250%)Max. time-delay fuse (175%)
200 V150 A187.5 A3/0 AWG400 A300 A
208 V143 A178.8 A3/0 AWG400 A300 A
230 V130 A162.5 A2/0 AWG350 A250 A
460 V65 A81.2 A4 AWG175 A125 A
575 V52 A65.0 A6 AWG150 A100 A

50 HP DC motor

50 HP direct-current motor
Armature voltageFull-load ampsConductor ampacity (125%)
240 V173 A216.2 A
500 V83 A103.8 A
550 V75 A93.8 A

50 HP two-phase motor

50 HP two-phase, 4-wire motor
VoltageFull-load amps
230 V113 A
460 V56 A
575 V45 A

50 HP is 37.30 kW of shaft output. Wire sizes above are the smallest copper conductor whose 75°C ampacity covers 125% of full-load current; 14 AWG is the practical minimum for power circuits. They do not include voltage drop — on long runs check the voltage drop calculator — or derating for hot locations or crowded conduits. Breaker and fuse values are maximums with the next-standard-size-up allowance applied; smaller devices are fine if the motor starts without tripping.

Motor wire & breaker size calculator

Loading calculator…

Other horsepower ratings

Frequently asked questions

How many amps does a 50 HP motor draw?

A 50 HP motor draws 130 A at 230 V and 65 A at 460 V three-phase. These are the code table values used for circuit sizing; the actual nameplate current is usually a little lower.

What size wire and breaker for a 50 HP three-phase motor at 460 V?

Full-load current is 65 A, so conductors need at least 81.2 A of ampacity: 4 AWG copper at 75°C. The inverse-time breaker may be up to 175 A and a dual-element time-delay fuse up to 125 A.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.