1-inch PVC Schedule 80 Conduit Fill

Wire capacity of trade size 1 (metric designator 27) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-inch PVC Schedule 80 holds 28 × #14, 20 × #12, 13 × #10 or 7 × #8 THHN conductors at 40% fill. Internal area: 0.688 in²; usable at 40%: 0.275 in².

Internal diameter
0.936 in · 23.8 mm
Total area
0.688 in² · 444 mm²
40% fill (3+ wires)
0.275 in²
31% / 53% (2 / 1 wire)
0.213 / 0.365 in²
Maximum conductors in 1-inch PVC Schedule 80
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG2819199420.0097
12 AWG2015157310.0133
10 AWG1311116190.0211
8 AWG7663110.0366
6 AWG543280.0507
4 AWG333150.0824
3 AWG331140.0973
2 AWG111130.1158
1 AWG111120.1562
1/0 AWG111120.1855
2/0 AWG111120.2223
3/0 AWG11110.2679
4/0 AWG1110.3237
250 kcmil10.3970
300 kcmil10.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-inch conduit: PVC Schedule 80 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.0490.8640.34626167
PVC Schedule 401.0290.8320.33325156
PVC Schedule 800.9360.6880.27520135
Rigid Metal Conduit1.0630.8870.35526177
IMC1.1050.9590.38429187
Flexible Metal Conduit1.0200.8170.32724156
Liquidtight Flexible Metal Conduit1.0540.8730.34926167
ENT1.0290.8320.33325156

Other PVC Schedule 80 sizes

Frequently asked questions

How many #12 wires fit in 1-inch PVC Schedule 80?

20 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 15.

What is the inside diameter and area of 1-inch PVC Schedule 80?

The internal diameter is 0.936 in. (23.8 mm) and the total cross-sectional area is 0.688 in². The usable area is 0.275 in² at 40% fill, 0.213 in² for two wires and 0.365 in² for one.

What is the largest wire I can pull three of in 1-inch PVC Schedule 80?

3 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 20 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.