1-inch IMC Conduit Fill

Wire capacity of trade size 1 (metric designator 27) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-inch IMC holds 39 × #14, 29 × #12, 18 × #10 or 10 × #8 THHN conductors at 40% fill. Internal area: 0.959 in²; usable at 40%: 0.384 in².

Internal diameter
1.105 in · 28.1 mm
Total area
0.959 in² · 619 mm²
40% fill (3+ wires)
0.384 in²
31% / 53% (2 / 1 wire)
0.297 / 0.508 in²
Maximum conductors in 1-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG39272713590.0097
12 AWG29212111430.0133
10 AWG1815158270.0211
8 AWG10884150.0366
6 AWG7653110.0507
4 AWG444370.0824
3 AWG443160.0973
2 AWG333150.1158
1 AWG111130.1562
1/0 AWG111130.1855
2/0 AWG111120.2223
3/0 AWG111120.2679
4/0 AWG111110.3237
250 kcmil11110.3970
300 kcmil1110.4608
350 kcmil10.5242
400 kcmil10.5863
500 kcmil10.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.0490.8640.34626167
PVC Schedule 401.0290.8320.33325156
PVC Schedule 800.9360.6880.27520135
Rigid Metal Conduit1.0630.8870.35526177
IMC1.1050.9590.38429187
Flexible Metal Conduit1.0200.8170.32724156
Liquidtight Flexible Metal Conduit1.0540.8730.34926167
ENT1.0290.8320.33325156

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 1-inch IMC?

29 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 21.

What is the inside diameter and area of 1-inch IMC?

The internal diameter is 1.105 in. (28.1 mm) and the total cross-sectional area is 0.959 in². The usable area is 0.384 in² at 40% fill, 0.297 in² for two wires and 0.508 in² for one.

What is the largest wire I can pull three of in 1-inch IMC?

2 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 29 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.