3/8-inch Flexible Metal (FMC) Conduit Fill

Wire capacity of trade size 3/8 (metric designator 12) Flexible Metal Conduit (FMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3/8-inch Flexible Metal Conduit holds 4 × #14, 3 × #12, 1 × #10 or 1 × #8 THHN conductors at 40% fill. Internal area: 0.116 in²; usable at 40%: 0.046 in².

Internal diameter
0.384 in · 9.8 mm
Total area
0.116 in² · 75 mm²
40% fill (3+ wires)
0.046 in²
31% / 53% (2 / 1 wire)
0.036 / 0.061 in²
Maximum conductors in 3/8-inch Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG433170.0097
12 AWG311150.0133
10 AWG111130.0211
8 AWG11120.0366
6 AWG1110.0507
4 AWG10.0824
3 AWG0.0973
2 AWG0.1158
1 AWG0.1562
1/0 AWG0.1855
2/0 AWG0.2223
3/0 AWG0.2679
4/0 AWG0.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

3/8-inch conduit: Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3/8-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
Flexible Metal Conduit0.3840.1160.046311
Liquidtight Flexible Metal Conduit0.4940.1920.077531

Other Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 3/8-inch Flexible Metal Conduit?

3 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 1.

What is the inside diameter and area of 3/8-inch Flexible Metal Conduit?

The internal diameter is 0.384 in. (9.8 mm) and the total cross-sectional area is 0.116 in². The usable area is 0.046 in² at 40% fill, 0.036 in² for two wires and 0.061 in² for one.

What is the largest wire I can pull three of in 3/8-inch Flexible Metal Conduit?

12 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.