1-1/4-inch Flexible Metal (FMC) Conduit Fill

Wire capacity of trade size 1-1/4 (metric designator 35) Flexible Metal Conduit (FMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/4-inch Flexible Metal Conduit holds 52 × #14, 38 × #12, 24 × #10 or 14 × #8 THHN conductors at 40% fill. Internal area: 1.277 in²; usable at 40%: 0.511 in².

Internal diameter
1.275 in · 32.4 mm
Total area
1.277 in² · 824 mm²
40% fill (3+ wires)
0.511 in²
31% / 53% (2 / 1 wire)
0.396 / 0.677 in²
Maximum conductors in 1-1/4-inch Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG52363617790.0097
12 AWG38282814570.0133
10 AWG24212111360.0211
8 AWG1411116210.0366
6 AWG10875150.0507
4 AWG665490.0824
3 AWG554380.0973
2 AWG444360.1158
1 AWG332150.1562
1/0 AWG221140.1855
2/0 AWG111130.2223
3/0 AWG111130.2679
4/0 AWG111120.3237
250 kcmil111120.3970
300 kcmil11110.4608
350 kcmil11110.5242
400 kcmil11110.5863
500 kcmil10.7073
600 kcmil10.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/4-inch conduit: Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.3801.4960.598452812
PVC Schedule 401.3601.4530.581432711
PVC Schedule 801.2551.2370.49537239
Rigid Metal Conduit1.3941.5260.610462912
IMC1.4481.6470.659493113
Flexible Metal Conduit1.2751.2770.511382410
Liquidtight Flexible Metal Conduit1.3951.5280.611462912
ENT1.3601.4530.581432711

Other Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 1-1/4-inch Flexible Metal Conduit?

38 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 28.

What is the inside diameter and area of 1-1/4-inch Flexible Metal Conduit?

The internal diameter is 1.275 in. (32.4 mm) and the total cross-sectional area is 1.277 in². The usable area is 0.511 in² at 40% fill, 0.396 in² for two wires and 0.677 in² for one.

What is the largest wire I can pull three of in 1-1/4-inch Flexible Metal Conduit?

1 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 38 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.