Flexible Metal (FMC) Conduit Fill Chart

Flexible Metal Conduit (FMC) — NEC Article 348. Spiral-wound interlocked steel or aluminum “Greenfield”. Used for short whips to motors, fixtures and equipment that vibrates or needs to move.

1/2-inch Flexible Metal Conduit holds 9 #12 THHN conductors; 3/4-inch holds 16. Counts assume 40% fill with all conductors the same size.

Flexible Metal Conduit fill calculator

Loading calculator…

Flexible Metal Conduit sizes

One page per trade size, with counts for every insulation type side by side.

Flexible Metal Conduit fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG41322335276135202291396518
12 AWG391624385698147212289378
10 AWG16101524356293134182238
8 AWG13691420355377105137
6 AWG114610142538557699
4 AWG124691624344661
3 AWG113571320293951
2 AWG113461117243343
1 AWG11134812182432
1/0 AWG1124710152027
2/0 AWG111369121722
3/0 AWG111257101418
4/0 AWG1114681215
250 kcmil111357912
300 kcmil11346811
350 kcmil1113579
400 kcmil1113568
500 kcmil112457
600 kcmil111345
700 kcmil11345
750 kcmil11234
800 kcmil11134
900 kcmil11134
1000 kcmil11133

Flexible Metal Conduit fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG391523365394141203277361
12 AWG171118284172108156212277
10 AWG1581321305481116158207
8 AWG1357111730456488115
6 AWG11358122233486585
4 AWG124691624344761
3 AWG113571320294052
2 AWG113461117243344
1 AWG11135813182532
1/0 AWG1124710152127
2/0 AWG111369131723
3/0 AWG111357101419
4/0 AWG1114691215
250 kcmil1113571013
300 kcmil11346811
350 kcmil1114579
400 kcmil1113568
500 kcmil113457
600 kcmil111345
700 kcmil11345
750 kcmil11234
800 kcmil11134
900 kcmil11134
1000 kcmil11133

Flexible Metal Conduit fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG391523365394141203277361
12 AWG171118284172108156212277
10 AWG1581321305481116158207
8 AWG1357111730456488115
6 AWG1347101827395369
4 AWG113571320293951
3 AWG113461117253444
2 AWG111451014212937
1 AWG1124710152026
1/0 AWG111369121722
2/0 AWG111357101419
3/0 AWG1114691216
4/0 AWG1113571013
250 kcmil11346811
300 kcmil1113579
350 kcmil1113468
400 kcmil1113467
500 kcmil111356
600 kcmil111345
700 kcmil11134
750 kcmil11134
800 kcmil11134
900 kcmil11133
1000 kcmil11123

Flexible Metal Conduit fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG147111725446796131171
12 AWG13691421375580109142
10 AWG1357111730456488115
8 AWG114691523344660
6 AWG113571219273748
4 AWG111451014212937
3 AWG11135813182533
2 AWG1134711162228
1 AWG111257101419
1/0 AWG1114691216
2/0 AWG1113581114
3/0 AWG111357912
4/0 AWG11246810
250 kcmil1113468
300 kcmil112457
350 kcmil111356
400 kcmil111346
500 kcmil11345
600 kcmil11134
700 kcmil11133
750 kcmil11123
800 kcmil11113
900 kcmil11113
1000 kcmil1113

Flexible Metal Conduit internal diameter and area

Flexible Metal Conduit internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
3/8"120.3840.1160.0610.0360.0460.070
1/2"160.6350.3170.1680.0980.1270.190
3/4"210.8240.5330.2820.1650.2130.320
1"271.0200.8170.4330.2530.3270.490
1-1/4"351.2751.2770.6770.3960.5110.766
1-1/2"411.5381.8580.9850.5760.7431.115
2"532.0403.2691.7331.0131.3081.961
2-1/2"632.5004.9092.6021.5221.9642.945
3"783.0007.0693.7472.1912.8284.241
3-1/2"913.5009.6215.0992.9833.8485.773
4"1034.00012.5666.6603.8955.0267.540

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch Flexible Metal Conduit?

9 conductors of 12 AWG THHN/THWN-2, or 7 of the thicker THW. In 3/4-inch Flexible Metal Conduit the count rises to 16 THHN.

How many #10 wires fit in 1/2-inch Flexible Metal Conduit?

6 conductors of 10 AWG THHN in 1/2-inch, and 10 in 3/4-inch.

What is the inside diameter of 3/4-inch Flexible Metal Conduit?

0.824 inches, giving a total internal area of 0.533 in² and 0.213 in² of usable area at 40% fill.

What is the largest wire that fits in 4-inch Flexible Metal Conduit?

4-inch Flexible Metal Conduit holds 7 conductors of 500 kcmil THHN or 3 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.