3-inch Flexible Metal (FMC) Conduit Fill

Wire capacity of trade size 3 (metric designator 78) Flexible Metal Conduit (FMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3-inch Flexible Metal Conduit holds 77 × #8, 55 × #6, 34 × #4 or 24 × #2 THHN conductors at 40% fill. Internal area: 7.069 in²; usable at 40%: 2.828 in².

Internal diameter
3.000 in · 76.2 mm
Total area
7.069 in² · 4561 mm²
40% fill (3+ wires)
2.828 in²
31% / 53% (2 / 1 wire)
2.191 / 3.747 in²
Maximum conductors in 3-inch Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG291203203964370.0097
12 AWG212156156803190.0133
10 AWG134116116642010.0211
8 AWG776464341160.0366
6 AWG55483927830.0507
4 AWG34342921510.0824
3 AWG29292518430.0973
2 AWG24242116360.1158
1 AWG18181510270.1562
1/0 AWG1515129230.1855
2/0 AWG1213108190.2223
3/0 AWG101097160.2679
4/0 AWG8976130.3237
250 kcmil7764100.3970
300 kcmil665490.4608
350 kcmil554380.5242
400 kcmil554370.5863
500 kcmil443360.7073
600 kcmil333150.8676
700 kcmil331140.9887
750 kcmil221141.0496
800 kcmil111141.1085
900 kcmil111131.2311
1000 kcmil111131.3478

Mixed wire sizes? Calculate it

Loading calculator…

3-inch conduit: Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT3.3568.8463.53826616769
PVC Schedule 403.0427.2682.90721813757
PVC Schedule 802.8646.4422.57719312251
Rigid Metal Conduit3.0907.4993.00022514259
IMC3.1767.9223.16923815062
Flexible Metal Conduit3.0007.0692.82821213455
Liquidtight Flexible Metal Conduit3.0857.4752.99022514159

Other Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 3-inch Flexible Metal Conduit?

212 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 156.

What is the inside diameter and area of 3-inch Flexible Metal Conduit?

The internal diameter is 3.000 in. (76.2 mm) and the total cross-sectional area is 7.069 in². The usable area is 2.828 in² at 40% fill, 2.191 in² for two wires and 3.747 in² for one.

What is the largest wire I can pull three of in 3-inch Flexible Metal Conduit?

700 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 212 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.