1-1/2-inch Flexible Metal (FMC) Conduit Fill

Wire capacity of trade size 1-1/2 (metric designator 41) Flexible Metal Conduit (FMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/2-inch Flexible Metal Conduit holds 76 × #14, 56 × #12, 35 × #10 or 20 × #8 THHN conductors at 40% fill. Internal area: 1.858 in²; usable at 40%: 0.743 in².

Internal diameter
1.538 in · 39.1 mm
Total area
1.858 in² · 1199 mm²
40% fill (3+ wires)
0.743 in²
31% / 53% (2 / 1 wire)
0.576 / 0.985 in²
Maximum conductors in 1-1/2-inch Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG765353251150.0097
12 AWG56414121840.0133
10 AWG35303017530.0211
8 AWG2017179300.0366
6 AWG1412107220.0507
4 AWG9975130.0824
3 AWG7765110.0973
2 AWG665490.1158
1 AWG454270.1562
1/0 AWG443160.1855
2/0 AWG333150.2223
3/0 AWG231140.2679
4/0 AWG111130.3237
250 kcmil111130.3970
300 kcmil111120.4608
350 kcmil111120.5242
400 kcmil111120.5863
500 kcmil11110.7073
600 kcmil11110.8676
700 kcmil10.9887
750 kcmil11.0496
800 kcmil11.1085
900 kcmil11.2311
1000 kcmil11.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/2-inch conduit: Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.6102.0360.814613816
PVC Schedule 401.5901.9860.794593715
PVC Schedule 801.4761.7110.684513213
Rigid Metal Conduit1.6242.0710.828623916
IMC1.6832.2250.890674217
Flexible Metal Conduit1.5381.8580.743563514
Liquidtight Flexible Metal Conduit1.5881.9810.792593715
ENT1.5901.9860.794593715

Other Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 1-1/2-inch Flexible Metal Conduit?

56 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 41.

What is the inside diameter and area of 1-1/2-inch Flexible Metal Conduit?

The internal diameter is 1.538 in. (39.1 mm) and the total cross-sectional area is 1.858 in². The usable area is 0.743 in² at 40% fill, 0.576 in² for two wires and 0.985 in² for one.

What is the largest wire I can pull three of in 1-1/2-inch Flexible Metal Conduit?

2/0 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 56 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.