3/4-inch Liquidtight (LFMC) Conduit Fill

Wire capacity of trade size 3/4 (metric designator 21) Liquidtight Flexible Metal Conduit (LFMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3/4-inch Liquidtight Flexible Metal Conduit holds 22 × #14, 16 × #12, 10 × #10 or 6 × #8 THHN conductors at 40% fill. Internal area: 0.541 in²; usable at 40%: 0.216 in².

Internal diameter
0.830 in · 21.1 mm
Total area
0.541 in² · 349 mm²
40% fill (3+ wires)
0.216 in²
31% / 53% (2 / 1 wire)
0.168 / 0.287 in²
Maximum conductors in 3/4-inch Liquidtight Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG2215157330.0097
12 AWG1612126240.0133
10 AWG10995150.0211
8 AWG655290.0366
6 AWG433160.0507
4 AWG221140.0824
3 AWG111130.0973
2 AWG111130.1158
1 AWG111120.1562
1/0 AWG11110.1855
2/0 AWG11110.2223
3/0 AWG1110.2679
4/0 AWG10.3237
250 kcmil10.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

3/4-inch conduit: Liquidtight Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT0.8240.5330.21316104
PVC Schedule 400.8040.5080.2031594
PVC Schedule 800.7220.4090.1641273
Rigid Metal Conduit0.8360.5490.22016104
IMC0.8640.5860.23417114
Flexible Metal Conduit0.8240.5330.21316104
Liquidtight Flexible Metal Conduit0.8300.5410.21616104
ENT0.8040.5080.2031594

Other Liquidtight Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 3/4-inch Liquidtight Flexible Metal Conduit?

16 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 12.

What is the inside diameter and area of 3/4-inch Liquidtight Flexible Metal Conduit?

The internal diameter is 0.830 in. (21.1 mm) and the total cross-sectional area is 0.541 in². The usable area is 0.216 in² at 40% fill, 0.168 in² for two wires and 0.287 in² for one.

What is the largest wire I can pull three of in 3/4-inch Liquidtight Flexible Metal Conduit?

6 AWG THHN: 4 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 16 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.