2-inch Liquidtight (LFMC) Conduit Fill

Wire capacity of trade size 2 (metric designator 53) Liquidtight Flexible Metal Conduit (LFMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

2-inch Liquidtight Flexible Metal Conduit holds 97 × #12, 61 × #10, 35 × #8 or 25 × #6 THHN conductors at 40% fill. Internal area: 3.246 in²; usable at 40%: 1.298 in².

Internal diameter
2.033 in · 51.6 mm
Total area
3.246 in² · 2094 mm²
40% fill (3+ wires)
1.298 in²
31% / 53% (2 / 1 wire)
1.006 / 1.720 in²
Maximum conductors in 2-inch Liquidtight Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG1349393442000.0097
12 AWG977171361460.0133
10 AWG61535329920.0211
8 AWG35292915530.0366
6 AWG25221812380.0507
4 AWG1516139230.0824
3 AWG1313118200.0973
2 AWG111197170.1158
1 AWG8875120.1562
1/0 AWG7764100.1855
2/0 AWG665380.2223
3/0 AWG554370.2679
4/0 AWG443260.3237
250 kcmil333150.3970
300 kcmil331140.4608
350 kcmil111130.5242
400 kcmil111130.5863
500 kcmil111120.7073
600 kcmil111120.8676
700 kcmil111120.9887
750 kcmil111121.0496
800 kcmil111111.1085
900 kcmil111111.2311
1000 kcmil11111.3478

Mixed wire sizes? Calculate it

Loading calculator…

2-inch conduit: Liquidtight Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT2.0673.3561.3421016326
PVC Schedule 402.0473.2911.316996226
PVC Schedule 801.9132.8741.150865422
Rigid Metal Conduit2.0833.4081.3631026427
IMC2.1503.6301.4521096928
Flexible Metal Conduit2.0403.2691.308986225
Liquidtight Flexible Metal Conduit2.0333.2461.298976125
ENT2.0473.2911.316996226

Other Liquidtight Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 2-inch Liquidtight Flexible Metal Conduit?

97 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 71.

What is the inside diameter and area of 2-inch Liquidtight Flexible Metal Conduit?

The internal diameter is 2.033 in. (51.6 mm) and the total cross-sectional area is 3.246 in². The usable area is 1.298 in² at 40% fill, 1.006 in² for two wires and 1.720 in² for one.

What is the largest wire I can pull three of in 2-inch Liquidtight Flexible Metal Conduit?

300 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 97 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.