Liquidtight (LFMC) Conduit Fill Chart

Liquidtight Flexible Metal Conduit (LFMC) — NEC Article 350. Flexible metal conduit with a sunlight- and oil-resistant thermoplastic jacket. The usual choice for outdoor equipment whips: air conditioners, pumps, rooftop units.

1/2-inch Liquidtight Flexible Metal Conduit holds 9 #12 THHN conductors; 3/4-inch holds 16. Counts assume 40% fill with all conductors the same size.

Liquidtight Flexible Metal Conduit fill calculator

Loading calculator…

Liquidtight Flexible Metal Conduit sizes

One page per trade size, with counts for every insulation type side by side.

Liquidtight Flexible Metal Conduit fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in Liquidtight Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG81322366381134201308401523
12 AWG591626465997146225292381
10 AWG36101629376192141184240
8 AWG13691621355381106138
6 AWG1147121525385976100
4 AWG1124791523364761
3 AWG1113681320304052
2 AWG113571117263344
1 AWG11145812192532
1/0 AWG1134710162127
2/0 AWG112368131723
3/0 AWG111357111419
4/0 AWG1114691215
250 kcmil1113571012
300 kcmil111346811
350 kcmil1113579
400 kcmil1113568
500 kcmil1112457
600 kcmil111346
700 kcmil111345
750 kcmil111335
800 kcmil11234
900 kcmil11134
1000 kcmil11133

Liquidtight Flexible Metal Conduit fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in Liquidtight Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG591525445793140215280365
12 AWG471219334371108165215280
10 AWG3591425325380123160209
8 AWG1358141829446889116
6 AWG113610132233506686
4 AWG1124791624364862
3 AWG1113681320314052
2 AWG113571117263444
1 AWG11145812192533
1/0 AWG1134710162128
2/0 AWG112369131723
3/0 AWG111357111419
4/0 AWG1114691216
250 kcmil1113571013
300 kcmil111346811
350 kcmil11135710
400 kcmil1113568
500 kcmil1112457
600 kcmil111346
700 kcmil111345
750 kcmil11335
800 kcmil11234
900 kcmil11134
1000 kcmil11133

Liquidtight Flexible Metal Conduit fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in Liquidtight Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG591525445793140215280365
12 AWG471219334371108165215280
10 AWG3591425325380123160209
8 AWG1358141829446889116
6 AWG11358111827415370
4 AWG1113681320304052
3 AWG113571117263444
2 AWG11246914222938
1 AWG1134710152026
1/0 AWG112368131723
2/0 AWG111357111519
3/0 AWG1114691216
4/0 AWG1113581013
250 kcmil111346811
300 kcmil1113579
350 kcmil1113568
400 kcmil1113467
500 kcmil1111356
600 kcmil111345
700 kcmil11234
750 kcmil11134
800 kcmil11134
900 kcmil11133
1000 kcmil11123

Liquidtight Flexible Metal Conduit fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in Liquidtight Flexible Metal Conduit — 40% fill (53% for one wire, 31% for two)
Wire size3/8"1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG2471221274466102133173
12 AWG136101722365584110144
10 AWG1358141829446889116
8 AWG1124791523364661
6 AWG113671218283748
4 AWG11246914222938
3 AWG11145813192533
2 AWG1134711172229
1 AWG111357111419
1/0 AWG11246101316
2/0 AWG1113581114
3/0 AWG111347912
4/0 AWG11246810
250 kcmil1113468
300 kcmil1112457
350 kcmil1111356
400 kcmil111346
500 kcmil111345
600 kcmil11134
700 kcmil11133
750 kcmil11123
800 kcmil11123
900 kcmil11113
1000 kcmil1113

Liquidtight Flexible Metal Conduit internal diameter and area

Liquidtight Flexible Metal Conduit internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
3/8"120.4940.1920.1020.0600.0770.115
1/2"160.6320.3140.1660.0970.1260.188
3/4"210.8300.5410.2870.1680.2160.325
1"271.0540.8730.4630.2710.3490.524
1-1/4"351.3951.5280.8100.4740.6110.917
1-1/2"411.5881.9811.0500.6140.7921.189
2"532.0333.2461.7201.0061.2981.948
2-1/2"632.4934.8812.5871.5131.9522.929
3"783.0857.4753.9622.3172.9904.485
3-1/2"913.5209.7315.1573.0173.8925.839
4"1034.02012.6926.7273.9355.0777.615

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch Liquidtight Flexible Metal Conduit?

9 conductors of 12 AWG THHN/THWN-2, or 7 of the thicker THW. In 3/4-inch Liquidtight Flexible Metal Conduit the count rises to 16 THHN.

How many #10 wires fit in 1/2-inch Liquidtight Flexible Metal Conduit?

6 conductors of 10 AWG THHN in 1/2-inch, and 10 in 3/4-inch.

What is the inside diameter of 3/4-inch Liquidtight Flexible Metal Conduit?

0.830 inches, giving a total internal area of 0.541 in² and 0.216 in² of usable area at 40% fill.

What is the largest wire that fits in 4-inch Liquidtight Flexible Metal Conduit?

4-inch Liquidtight Flexible Metal Conduit holds 7 conductors of 500 kcmil THHN or 3 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.