1-1/4-inch Liquidtight (LFMC) Conduit Fill

Wire capacity of trade size 1-1/4 (metric designator 35) Liquidtight Flexible Metal Conduit (LFMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

1-1/4-inch Liquidtight Flexible Metal Conduit holds 63 × #14, 46 × #12, 29 × #10 or 16 × #8 THHN conductors at 40% fill. Internal area: 1.528 in²; usable at 40%: 0.611 in².

Internal diameter
1.395 in · 35.4 mm
Total area
1.528 in² · 986 mm²
40% fill (3+ wires)
0.611 in²
31% / 53% (2 / 1 wire)
0.474 / 0.810 in²
Maximum conductors in 1-1/4-inch Liquidtight Flexible Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG63444421940.0097
12 AWG46333317690.0133
10 AWG29252514430.0211
8 AWG1614147250.0366
6 AWG121086180.0507
4 AWG7764110.0824
3 AWG665490.0973
2 AWG554380.1158
1 AWG443160.1562
1/0 AWG332150.1855
2/0 AWG221140.2223
3/0 AWG111130.2679
4/0 AWG111130.3237
250 kcmil111120.3970
300 kcmil111120.4608
350 kcmil111110.5242
400 kcmil11110.5863
500 kcmil11110.7073
600 kcmil10.8676
700 kcmil10.9887
750 kcmil11.0496
800 kcmil11.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

1-1/4-inch conduit: Liquidtight Flexible Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

1-1/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT1.3801.4960.598452812
PVC Schedule 401.3601.4530.581432711
PVC Schedule 801.2551.2370.49537239
Rigid Metal Conduit1.3941.5260.610462912
IMC1.4481.6470.659493113
Flexible Metal Conduit1.2751.2770.511382410
Liquidtight Flexible Metal Conduit1.3951.5280.611462912
ENT1.3601.4530.581432711

Other Liquidtight Flexible Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 1-1/4-inch Liquidtight Flexible Metal Conduit?

46 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 33.

What is the inside diameter and area of 1-1/4-inch Liquidtight Flexible Metal Conduit?

The internal diameter is 1.395 in. (35.4 mm) and the total cross-sectional area is 1.528 in². The usable area is 0.611 in² at 40% fill, 0.474 in² for two wires and 0.810 in² for one.

What is the largest wire I can pull three of in 1-1/4-inch Liquidtight Flexible Metal Conduit?

1/0 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 46 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.