3/4-inch PVC Schedule 80 Conduit Fill

Wire capacity of trade size 3/4 (metric designator 21) Rigid PVC Conduit, Schedule 80, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3/4-inch PVC Schedule 80 holds 17 × #14, 12 × #12, 7 × #10 or 4 × #8 THHN conductors at 40% fill. Internal area: 0.409 in²; usable at 40%: 0.164 in².

Internal diameter
0.722 in · 18.3 mm
Total area
0.409 in² · 264 mm²
40% fill (3+ wires)
0.164 in²
31% / 53% (2 / 1 wire)
0.127 / 0.217 in²
Maximum conductors in 3/4-inch PVC Schedule 80
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG1711115250.0097
12 AWG12994180.0133
10 AWG7663110.0211
8 AWG433160.0366
6 AWG321150.0507
4 AWG111130.0824
3 AWG111120.0973
2 AWG111120.1158
1 AWG11110.1562
1/0 AWG1110.1855
2/0 AWG10.2223
3/0 AWG10.2679
4/0 AWG0.3237
250 kcmil0.3970
300 kcmil0.4608
350 kcmil0.5242
400 kcmil0.5863
500 kcmil0.7073
600 kcmil0.8676
700 kcmil0.9887
750 kcmil1.0496
800 kcmil1.1085
900 kcmil1.2311
1000 kcmil1.3478

Mixed wire sizes? Calculate it

Loading calculator…

3/4-inch conduit: PVC Schedule 80 vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3/4-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT0.8240.5330.21316104
PVC Schedule 400.8040.5080.2031594
PVC Schedule 800.7220.4090.1641273
Rigid Metal Conduit0.8360.5490.22016104
IMC0.8640.5860.23417114
Flexible Metal Conduit0.8240.5330.21316104
Liquidtight Flexible Metal Conduit0.8300.5410.21616104
ENT0.8040.5080.2031594

Other PVC Schedule 80 sizes

Frequently asked questions

How many #12 wires fit in 3/4-inch PVC Schedule 80?

12 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 9.

What is the inside diameter and area of 3/4-inch PVC Schedule 80?

The internal diameter is 0.722 in. (18.3 mm) and the total cross-sectional area is 0.409 in². The usable area is 0.164 in² at 40% fill, 0.127 in² for two wires and 0.217 in² for one.

What is the largest wire I can pull three of in 3/4-inch PVC Schedule 80?

6 AWG THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 12 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.