3-1/2-inch Rigid Metal (RMC) Conduit Fill

Wire capacity of trade size 3-1/2 (metric designator 91) Rigid Metal Conduit (RMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3-1/2-inch Rigid Metal Conduit holds 79 × #6, 48 × #4, 34 × #2 or 21 × 1/0 AWG THHN conductors at 40% fill. Internal area: 10.010 in²; usable at 40%: 4.004 in².

Internal diameter
3.570 in · 90.7 mm
Total area
10.010 in² · 6458 mm²
40% fill (3+ wires)
4.004 in²
31% / 53% (2 / 1 wire)
3.103 / 5.305 in²
Maximum conductors in 3-1/2-inch Rigid Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG4122882881366190.0097
12 AWG3012212211134510.0133
10 AWG189164164912840.0211
8 AWG1099191481640.0366
6 AWG796855381180.0507
4 AWG48494130730.0824
3 AWG41413526610.0973
2 AWG34353023520.1158
1 AWG25262115380.1562
1/0 AWG21221813320.1855
2/0 AWG18181511270.2223
3/0 AWG15151310220.2679
4/0 AWG1212108180.3237
250 kcmil101086150.3970
300 kcmil8975130.4608
350 kcmil7765110.5242
400 kcmil7764100.5863
500 kcmil555480.7073
600 kcmil444370.8676
700 kcmil443360.9887
750 kcmil443351.0496
800 kcmil333251.1085
900 kcmil333151.2311
1000 kcmil332141.3478

Mixed wire sizes? Calculate it

Loading calculator…

3-1/2-inch conduit: Rigid Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3-1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT3.83411.5454.61834721991
PVC Schedule 403.5219.7373.89529318477
PVC Schedule 803.3268.6883.47526116468
Rigid Metal Conduit3.57010.0104.00430118979
IMC3.67110.5844.23431820083
Flexible Metal Conduit3.5009.6213.84828918276
Liquidtight Flexible Metal Conduit3.5209.7313.89229218476

Other Rigid Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 3-1/2-inch Rigid Metal Conduit?

301 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 221.

What is the inside diameter and area of 3-1/2-inch Rigid Metal Conduit?

The internal diameter is 3.570 in. (90.7 mm) and the total cross-sectional area is 10.010 in². The usable area is 4.004 in² at 40% fill, 3.103 in² for two wires and 5.305 in² for one.

What is the largest wire I can pull three of in 3-1/2-inch Rigid Metal Conduit?

1000 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 301 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.