6-inch Rigid Metal (RMC) Conduit Fill

Wire capacity of trade size 6 (metric designator 155) Rigid Metal Conduit (RMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

6-inch Rigid Metal Conduit holds 63 × 1/0 AWG, 36 × 4/0 AWG, 16 × 500 kcmil or 11 × 750 kcmil THHN conductors at 40% fill. Internal area: 29.158 in²; usable at 40%: 11.663 in².

Internal diameter
6.093 in · 154.8 mm
Total area
29.158 in² · 18812 mm²
40% fill (3+ wires)
11.663 in²
31% / 53% (2 / 1 wire)
9.039 / 15.454 in²
Maximum conductors in 6-inch Rigid Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG120283983939818030.0097
12 AWG87764464433013150.0133
10 AWG5524804802678290.0211
8 AWG3182672671394780.0366
6 AWG2301971601123450.0507
4 AWG141143120872120.0824
3 AWG120121103761800.0973
2 AWG10010187661510.1158
1 AWG747661441120.1562
1/0 AWG63645238940.1855
2/0 AWG52534433780.2223
3/0 AWG43443728650.2679
4/0 AWG36363124540.3237
250 kcmil29302518440.3970
300 kcmil25252216380.4608
350 kcmil22221915330.5242
400 kcmil20201713300.5863
500 kcmil16161411240.7073
600 kcmil1313129200.8676
700 kcmil1111108170.9887
750 kcmil1111108161.0496
800 kcmil101097151.1085
900 kcmil9987141.2311
1000 kcmil8886131.3478

Mixed wire sizes? Calculate it

Loading calculator…

6-inch conduit: Rigid Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

6-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
PVC Schedule 406.03128.56711.427859541225
PVC Schedule 805.70925.59810.239770485202
Rigid Metal Conduit6.09329.15811.663877552230

Other Rigid Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 6-inch Rigid Metal Conduit?

877 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 644.

What is the inside diameter and area of 6-inch Rigid Metal Conduit?

The internal diameter is 6.093 in. (154.8 mm) and the total cross-sectional area is 29.158 in². The usable area is 11.663 in² at 40% fill, 9.039 in² for two wires and 15.454 in² for one.

What is the largest wire I can pull three of in 6-inch Rigid Metal Conduit?

1000 kcmil THHN: 8 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 877 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.