3-1/2-inch IMC Conduit Fill

Wire capacity of trade size 3-1/2 (metric designator 91) Intermediate Metal Conduit, for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

3-1/2-inch IMC holds 83 × #6, 51 × #4, 36 × #2 or 23 × 1/0 AWG THHN conductors at 40% fill. Internal area: 10.584 in²; usable at 40%: 4.234 in².

Internal diameter
3.671 in · 93.2 mm
Total area
10.584 in² · 6828 mm²
40% fill (3+ wires)
4.234 in²
31% / 53% (2 / 1 wire)
3.281 / 5.610 in²
Maximum conductors in 3-1/2-inch IMC
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG4363043041446540.0097
12 AWG3182342341204770.0133
10 AWG200174174973010.0211
8 AWG1159797501730.0366
6 AWG837158401250.0507
4 AWG51524331770.0824
3 AWG43443728650.0973
2 AWG36373124550.1158
1 AWG27272216400.1562
1/0 AWG23231914340.1855
2/0 AWG19191612280.2223
3/0 AWG16161310230.2679
4/0 AWG1313119190.3237
250 kcmil101196160.3970
300 kcmil9986130.4608
350 kcmil8875120.5242
400 kcmil7765110.5863
500 kcmil665490.7073
600 kcmil554370.8676
700 kcmil444360.9887
750 kcmil443361.0496
800 kcmil443351.1085
900 kcmil333251.2311
1000 kcmil333141.3478

Mixed wire sizes? Calculate it

Loading calculator…

3-1/2-inch conduit: IMC vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

3-1/2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT3.83411.5454.61834721991
PVC Schedule 403.5219.7373.89529318477
PVC Schedule 803.3268.6883.47526116468
Rigid Metal Conduit3.57010.0104.00430118979
IMC3.67110.5844.23431820083
Flexible Metal Conduit3.5009.6213.84828918276
Liquidtight Flexible Metal Conduit3.5209.7313.89229218476

Other IMC sizes

Frequently asked questions

How many #12 wires fit in 3-1/2-inch IMC?

318 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 234.

What is the inside diameter and area of 3-1/2-inch IMC?

The internal diameter is 3.671 in. (93.2 mm) and the total cross-sectional area is 10.584 in². The usable area is 4.234 in² at 40% fill, 3.281 in² for two wires and 5.610 in² for one.

What is the largest wire I can pull three of in 3-1/2-inch IMC?

1000 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 318 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.