2-inch Rigid Metal (RMC) Conduit Fill

Wire capacity of trade size 2 (metric designator 53) Rigid Metal Conduit (RMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

2-inch Rigid Metal Conduit holds 64 × #10, 37 × #8, 27 × #6 or 16 × #4 THHN conductors at 40% fill. Internal area: 3.408 in²; usable at 40%: 1.363 in².

Internal diameter
2.083 in · 52.9 mm
Total area
3.408 in² · 2199 mm²
40% fill (3+ wires)
1.363 in²
31% / 53% (2 / 1 wire)
1.056 / 1.806 in²
Maximum conductors in 2-inch Rigid Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG1409898462110.0097
12 AWG1027575381530.0133
10 AWG64565631970.0211
8 AWG37313116560.0366
6 AWG27231813400.0507
4 AWG16161410250.0824
3 AWG1414129210.0973
2 AWG1112107170.1158
1 AWG8975130.1562
1/0 AWG7764110.1855
2/0 AWG665490.2223
3/0 AWG554370.2679
4/0 AWG443360.3237
250 kcmil333150.3970
300 kcmil332140.4608
350 kcmil221140.5242
400 kcmil111130.5863
500 kcmil111130.7073
600 kcmil111120.8676
700 kcmil111120.9887
750 kcmil111121.0496
800 kcmil111121.1085
900 kcmil111111.2311
1000 kcmil111111.3478

Mixed wire sizes? Calculate it

Loading calculator…

2-inch conduit: Rigid Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

2-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
EMT2.0673.3561.3421016326
PVC Schedule 402.0473.2911.316996226
PVC Schedule 801.9132.8741.150865422
Rigid Metal Conduit2.0833.4081.3631026427
IMC2.1503.6301.4521096928
Flexible Metal Conduit2.0403.2691.308986225
Liquidtight Flexible Metal Conduit2.0333.2461.298976125
ENT2.0473.2911.316996226

Other Rigid Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 2-inch Rigid Metal Conduit?

102 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 75.

What is the inside diameter and area of 2-inch Rigid Metal Conduit?

The internal diameter is 2.083 in. (52.9 mm) and the total cross-sectional area is 3.408 in². The usable area is 1.363 in² at 40% fill, 1.056 in² for two wires and 1.806 in² for one.

What is the largest wire I can pull three of in 2-inch Rigid Metal Conduit?

300 kcmil THHN: 3 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 102 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.