5-inch Rigid Metal (RMC) Conduit Fill

Wire capacity of trade size 5 (metric designator 129) Rigid Metal Conduit (RMC), for THHN, XHHW, THW and RHW conductors from 14 AWG to 1000 kcmil.

5-inch Rigid Metal Conduit holds 98 × #4, 70 × #2, 43 × 1/0 AWG or 25 × 4/0 AWG THHN conductors at 40% fill. Internal area: 20.212 in²; usable at 40%: 8.085 in².

Internal diameter
5.073 in · 128.9 mm
Total area
20.212 in² · 13040 mm²
40% fill (3+ wires)
8.085 in²
31% / 53% (2 / 1 wire)
6.266 / 10.712 in²
Maximum conductors in 5-inch Rigid Metal Conduit
Wire sizeTHHNXHHWTHWRHWTHHN in a nipple (60%)THHN area (in²)
14 AWG83358158127612500.0097
12 AWG6084464462299120.0133
10 AWG3833323321855740.0211
8 AWG221185185973310.0366
6 AWG159137111772390.0507
4 AWG989983601470.0824
3 AWG838471531240.0973
2 AWG707060461040.1158
1 AWG51524230770.1562
1/0 AWG43443626650.1855
2/0 AWG36373123540.2223
3/0 AWG30302620450.2679
4/0 AWG25252117370.3237
250 kcmil20201713300.3970
300 kcmil17181511260.4608
350 kcmil15151310230.5242
400 kcmil1314129200.5863
500 kcmil1111108170.7073
600 kcmil9986140.8676
700 kcmil8876120.9887
750 kcmil7775111.0496
800 kcmil7765111.1085
900 kcmil6665101.2311
1000 kcmil665491.3478

Mixed wire sizes? Calculate it

Loading calculator…

5-inch conduit: Rigid Metal Conduit vs other types

Trade size is nominal. The real inside diameter, and so the wire count, changes with the wall thickness of each raceway type.

5-inch trade size across conduit types
Conduit typeID (in)Area (in²)40% (in²)#12 THHN#10 THHN#6 THHN
PVC Schedule 405.01619.7617.904594374156
PVC Schedule 804.76817.8557.142537338141
Rigid Metal Conduit5.07320.2128.085608383159

Other Rigid Metal Conduit sizes

Frequently asked questions

How many #12 wires fit in 5-inch Rigid Metal Conduit?

608 conductors of 12 AWG THHN/THWN-2 at the 40% fill limit. With thicker THW or XHHW insulation the count is 446.

What is the inside diameter and area of 5-inch Rigid Metal Conduit?

The internal diameter is 5.073 in. (128.9 mm) and the total cross-sectional area is 20.212 in². The usable area is 8.085 in² at 40% fill, 6.266 in² for two wires and 10.712 in² for one.

What is the largest wire I can pull three of in 5-inch Rigid Metal Conduit?

1000 kcmil THHN: 6 conductors fit at 40% fill. That is three current-carrying conductors with no ground; add the ground’s area and check again with the calculator if you need one.

Can I really load it with that many conductors?

For space, yes. But 608 current-carrying conductors in one raceway means heavy ampacity derating — 10 to 20 conductors are adjusted to 50% of their table ampacity. Fill tells you what fits; derating tells you what it can carry.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.