PVC Schedule 80 Conduit Fill Chart

Rigid PVC Conduit, Schedule 80 — NEC Article 352. Heavy-wall PVC required where conduit is exposed to physical damage, such as risers on poles and service masts. Same outside diameter as Schedule 40, so the thicker wall takes noticeably more room from the inside.

1/2-inch PVC Schedule 80 holds 6 #12 THHN conductors; 3/4-inch holds 12. Counts assume 40% fill with all conductors the same size.

PVC Schedule 80 fill calculator

Loading calculator…

PVC Schedule 80 sizes

One page per trade size, with counts for every insulation type side by side.

PVC Schedule 80 fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in PVC Schedule 80 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG9172851701181702653584647361055
12 AWG61220375186124193261338537770
10 AWG471323325478122164213338485
8 AWG147131831457095123195279
6 AWG1359132232516889141202
4 AWG11368142031425486124
3 AWG11357121726354673105
2 AWG114610142230396188
1 AWG11347101622294565
1/0 AWG1123691418243855
2/0 AWG113571115203246
3/0 AWG11146913172638
4/0 AWG11135810142231
250 kcmil113468111825
300 kcmil11135791522
350 kcmil11135681319
400 kcmil11134671217
500 kcmil1113561014
600 kcmil111345812
700 kcmil11234710
750 kcmil1113479
800 kcmil1113469
900 kcmil1113368
1000 kcmil1111357

PVC Schedule 80 fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in PVC Schedule 80 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG61119354982118185250324514736
12 AWG491527386391142192248394565
10 AWG361120284768106143185294421
8 AWG136111526375979103163234
6 AWG1248111928435976121173
4 AWG11368142031425587125
3 AWG11357121726364774106
2 AWG1114610142230396289
1 AWG11347101622294666
1/0 AWG1123691419243956
2/0 AWG113571116203246
3/0 AWG11246913172738
4/0 AWG11135811142232
250 kcmil113469111826
300 kcmil111357101522
350 kcmil11135681420
400 kcmil11134671217
500 kcmil1113561014
600 kcmil111345811
700 kcmil11234710
750 kcmil1113469
800 kcmil1113469
900 kcmil1113358
1000 kcmil1111357

PVC Schedule 80 fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in PVC Schedule 80 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG61119354982118185250324514736
12 AWG491527386391142192248394565
10 AWG361120284768106143185294421
8 AWG136111526375979103163234
6 AWG11379162235486298141
4 AWG11357121726354673105
3 AWG1114610142230396390
2 AWG11358121926335377
1 AWG1123681318233754
1/0 AWG113571115203246
2/0 AWG112461013172739
3/0 AWG11135811142333
4/0 AWG113479121927
250 kcmil11135791522
300 kcmil11135681319
350 kcmil11124671217
400 kcmil1114571015
500 kcmil111345913
600 kcmil11234710
700 kcmil1113469
750 kcmil1113468
800 kcmil1113368
900 kcmil1111357
1000 kcmil1111357

PVC Schedule 80 fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in PVC Schedule 80 — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"5"6"
14 AWG3591723395688118153243349
12 AWG147141932467398127202290
10 AWG136111526375979103163234
8 AWG11368131931415485122
6 AWG1124611162433436898
4 AWG11358121926335377
3 AWG11347111723294767
2 AWG1134691420254158
1 AWG11146913172738
1/0 AWG11135811152333
2/0 AWG11134710132029
3/0 AWG113468111725
4/0 AWG11135791521
250 kcmil11124571116
300 kcmil1113561014
350 kcmil111345913
400 kcmil111345812
500 kcmil11134710
600 kcmil1113368
700 kcmil1111357
750 kcmil1111357
800 kcmil1111347
900 kcmil111246
1000 kcmil111145

PVC Schedule 80 internal diameter and area

PVC Schedule 80 internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
1/2"160.5260.2170.1150.0670.0870.130
3/4"210.7220.4090.2170.1270.1640.245
1"270.9360.6880.3650.2130.2750.413
1-1/4"351.2551.2370.6560.3830.4950.742
1-1/2"411.4761.7110.9070.5300.6841.027
2"531.9132.8741.5230.8911.1501.724
2-1/2"632.2904.1192.1831.2771.6482.471
3"782.8646.4423.4141.9972.5773.865
3-1/2"913.3268.6884.6052.6933.4755.213
4"1033.78611.2585.9673.4904.5036.755
5"1294.76817.8559.4635.5357.14210.713
6"1555.70925.59813.5677.93510.23915.359

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch PVC Schedule 80?

6 conductors of 12 AWG THHN/THWN-2, or 4 of the thicker THW. In 3/4-inch PVC Schedule 80 the count rises to 12 THHN.

How many #10 wires fit in 1/2-inch PVC Schedule 80?

4 conductors of 10 AWG THHN in 1/2-inch, and 7 in 3/4-inch.

What is the inside diameter of 3/4-inch PVC Schedule 80?

0.722 inches, giving a total internal area of 0.409 in² and 0.164 in² of usable area at 40% fill.

What is the largest wire that fits in 6-inch PVC Schedule 80?

6-inch PVC Schedule 80 holds 14 conductors of 500 kcmil THHN or 7 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.