IMC Conduit Fill Chart

Intermediate Metal Conduit — NEC Article 342. Threaded steel conduit with a thinner wall than rigid. Permitted everywhere RMC is, weighs about a third less, and has the largest interior of the three steel raceways.

1/2-inch IMC holds 10 #12 THHN conductors; 3/4-inch holds 17. Counts assume 40% fill with all conductors the same size.

IMC fill calculator

Loading calculator…

IMC sizes

One page per trade size, with counts for every insulation type side by side.

IMC fill chart — THHN / THWN-2

Thermoplastic insulation with a nylon jacket. The thinnest common building wire, so it gives the highest conductor counts. Nearly all pulled wire sold in North America is dual-rated THHN/THWN-2.

Maximum THHN conductors in IMC — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1424396891149211326436562
12 AWG1017294967109154238318410
10 AWG6111831426997150200258
8 AWG36101824395686115149
6 AWG247131728406283107
4 AWG1348111725385166
3 AWG114691521324356
2 AWG113571217273647
1 AWG11145913202735
1/0 AWG1134811172329
2/0 AWG113469141924
3/0 AWG111357121620
4/0 AWG1124691317
250 kcmil1113581013
300 kcmil111347912
350 kcmil11246810
400 kcmil1113579
500 kcmil1113467
600 kcmil1111356
700 kcmil111345
750 kcmil111345
800 kcmil111345
900 kcmil11134
1000 kcmil11134

IMC fill chart — XHHW / XHHW-2

Cross-linked polyethylene (XLPE) insulation, no nylon jacket. Standard for aluminum feeders and common for larger copper feeders. Slightly fatter than THHN in small sizes, slightly thinner above 4 AWG.

Maximum XHHW conductors in IMC — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1017274764104147228304392
12 AWG71321364980113175234301
10 AWG591527365984130174224
8 AWG358152033477297124
6 AWG14611152435537192
4 AWG1348111825395267
3 AWG114791521334456
2 AWG113571218273747
1 AWG11146913202735
1/0 AWG1135811172330
2/0 AWG113469141925
3/0 AWG111357121620
4/0 AWG11246101317
250 kcmil1113581114
300 kcmil111347912
350 kcmil11346810
400 kcmil1113579
500 kcmil1113468
600 kcmil1111356
700 kcmil111345
750 kcmil111345
800 kcmil111345
900 kcmil11134
1000 kcmil11134

IMC fill chart — THW / THHW / TW

Older thick-wall thermoplastic insulation without a nylon jacket. Rarely installed new, but it is what you will find in many existing conduits, and it takes considerably more room than THHN.

Maximum THW conductors in IMC — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1017274764104147228304392
12 AWG71321364980113175234301
10 AWG591527365984130174224
8 AWG358152033477297124
6 AWG1359122028435875
4 AWG114691521324356
3 AWG113681318283748
2 AWG113561115233141
1 AWG1134711162228
1/0 AWG113469141924
2/0 AWG111358121620
3/0 AWG11346101317
4/0 AWG1114581114
250 kcmil111347912
300 kcmil11246810
350 kcmil1113579
400 kcmil1113468
500 kcmil1112457
600 kcmil111345
700 kcmil111345
750 kcmil111234
800 kcmil11234
900 kcmil11134
1000 kcmil11133

IMC fill chart — RHH / RHW-2

Thermoset rubber-type insulation with an outer covering. The bulkiest of the common types; counts drop to roughly half of THHN in small conduit.

Maximum RHW conductors in IMC — 40% fill (53% for one wire, 31% for two)
Wire size1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG481322304970108144186
12 AWG46111825415889120154
10 AWG358152033477297124
8 AWG1348101724385065
6 AWG113681419304052
4 AWG113561115233141
3 AWG11146913212836
2 AWG11135811182431
1 AWG111357121620
1/0 AWG111346101418
2/0 AWG1114691215
3/0 AWG1113571013
4/0 AWG111346911
250 kcmil1113568
300 kcmil1113467
350 kcmil1112457
400 kcmil1111356
500 kcmil111345
600 kcmil11234
700 kcmil11134
750 kcmil11134
800 kcmil11133
900 kcmil11123
1000 kcmil11113

IMC internal diameter and area

IMC internal dimensions and allowable fill area
Trade sizeMetric designatorInternal dia. (in)Total area (in²)1 wire — 53%2 wires — 31%Over 2 — 40%Nipple — 60%
1/2"160.6600.3420.1810.1060.1370.205
3/4"210.8640.5860.3110.1820.2340.352
1"271.1050.9590.5080.2970.3840.575
1-1/4"351.4481.6470.8730.5110.6590.988
1-1/2"411.6832.2251.1790.6900.8901.335
2"532.1503.6301.9241.1251.4522.178
2-1/2"632.5575.1352.7221.5922.0543.081
3"783.1767.9224.1992.4563.1694.753
3-1/2"913.67110.5845.6103.2814.2346.350
4"1034.16613.6317.2244.2265.4528.179

Fill limits that apply

Allowable conduit fill (Chapter 9, Table 1 and its notes)
Conductors in the racewayMaximum fillWhy
153%A single conductor cannot jam, so more of the area can be used.
231%Two conductors lie side by side and wedge easily in bends, so the limit is lowest.
3 or more40%The everyday limit. Leaves room to pull and for heat to escape.
Nipple ≤ 24 in.60%Short sections between boxes or enclosures; derating for conductor count does not apply either.

Frequently asked questions

How many #12 wires can I put in 1/2-inch IMC?

10 conductors of 12 AWG THHN/THWN-2, or 7 of the thicker THW. In 3/4-inch IMC the count rises to 17 THHN.

How many #10 wires fit in 1/2-inch IMC?

6 conductors of 10 AWG THHN in 1/2-inch, and 11 in 3/4-inch.

What is the inside diameter of 3/4-inch IMC?

0.864 inches, giving a total internal area of 0.586 in² and 0.234 in² of usable area at 40% fill.

What is the largest wire that fits in 4-inch IMC?

4-inch IMC holds 7 conductors of 500 kcmil THHN or 4 of 1000 kcmil.

NECTables.com is an independent reference and is not affiliated with, endorsed by, or a substitute for the National Fire Protection Association (NFPA). NEC® and National Electrical Code® are registered trademarks of the NFPA. Values shown are commonly published engineering data and independent calculations based on the methods of NFPA 70; they are not a reproduction of the Code. Always confirm against the edition adopted in your jurisdiction, including local amendments, and consult a licensed electrician or engineer before doing electrical work.